| General |
| Model | Wall surface mounted |
| Material | Plastic |
| Colour | RAL 7035 |
| Scope of delivery | 1 cover (front side) |
| Fan | Axial, split-pole motor |
| Airflow free blowing (with pleated filter) | At 50 Hz: 110 m³/h, At 60 Hz: 125 m³/h |
| Airflow with associated exhaust filter including pleated filter | At 50 Hz: 92 m³/h, At 60 Hz: 104 m³/h |
| Airflow free-blowing (with filter) | At 50 Hz: 100 m³/h, At 60 Hz: 115 m³/h |
| Airflow with associated exhaust filter including felt filter | At 50 Hz: 75 m³/h, At 60 Hz: 86 m³/h |
| Rated operating voltage | 115 V, 1~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 15.4 W, at 60 Hz: 15.8 W |
| Rated current max. | At 50 Hz: 0.2 A, At 60 Hz: 0.21 A |
| Width | 204 mm |
| Height | 204 mm |
| Depth | 105 mm |
| Built-in depth | 84 mm |
| Mounting cutout | Cutout width: 177 mm, cutout height: 177 mm |
| Degree of protection IP according to IEC 60 529 | IP 54 with nonwoven filter/pleated filter, IP 55 with pleated filter and absorber mat, IP 56 with nonwoven filter/pleated filter and spray water hood |
| NEMA degree of protection | Type 12 with felt filter/pleated filter, Type 3, 3R, 4, 4X with felt filter/pleated filter and spray water hood |
| Fuse | Circuit breaker/fuse: 2 A |
| Note | For the filter fan 3237.XXX, the electrical connection is made via 2 individual wires (approx. 300 mm length) on the device; for all other filter fans, via spring clamp terminal. |
| Operating temperature range | -15 °C...55 °C |
| Storage temperature range | -30 °C...70 °C |
| Sound pressure level | At 50 Hz: 51 dB(A), At 60 Hz: 54 dB(A) |
The Rittal SK 3239.710 is a
filter fan from the SK Blue e+ series, designed for
enclosure climate control in industrial applications. The device is mounted as a
wall-mounted installation and serves for controlled ventilation of enclosures, regulating internal temperature and extending the service life of electronic components. It features
diagonal fan technology, enabling higher pressure stability and more even air distribution within the enclosure. The diagonal airflow direction ensures more consistent air performance and more efficient cooling of devices inside the enclosure.
Applications
The filter fan is suitable for use in industrial environments where continuous ventilation is required to control operating temperature within the enclosure. It is particularly suited for installations operated in rooms with moderate dust and humidity levels. The integrated filter technology protects the interior of the enclosure from particles and prevents dust accumulation on electronic components. The protection rating IP 54 is standard, and higher protection levels up to IP 56 can be achieved with additional components such as absorber mat or spray water hood.
Functions and Equipment in Detail
The device is supplied with a
pleated filter as standard, enabling a maximum free-blowing air performance of 110 m³/h at 50 Hz and 125 m³/h at 60 Hz. When using a matching
outlet filter, air performance drops to 92 m³/h (50 Hz) or 104 m³/h (60 Hz). Alternatively, a
nonwoven filter can be used, providing free-blowing air performance of 100 m³/h (50 Hz) or 115 m³/h (60 Hz), with performance decreasing to 75 m³/h (50 Hz) or 86 m³/h (60 Hz) when an outlet filter is used. Air performance depends on the frequency of the operating voltage and is influenced by the filter type. The fan is equipped with an
axial fan based on a
split-pole motor. The rated operating voltage is 115 V, 1~, designed for frequencies of 50 Hz and 60 Hz. The rated power is 15.4 W (50 Hz) or 15.8 W (60 Hz), and the maximum rated current is 0.2 A (50 Hz) or 0.21 A (60 Hz). The fuse is rated at 2 A.
Technology Explained Simply
The diagonal fan technology ensures that air flows diagonally rather than vertically from the device. This results in better pressure stability and more even air distribution within the enclosure, improving cooling performance. The integrated filter technology ensures that dust particles and other contaminants are filtered from the incoming air before entering the enclosure. Filter replacement is simplified by a new opening mechanism on the louver grille. Installation is tool-free via optimized snap hooks, accelerating mounting on the enclosure. The installation depth is 84 mm, and the mounting cutout measures 177 mm in width and height. The device is made of
plastic and is available in the color
RAL 7035.
Compatibility and Accessories
The filter fan can be combined with various accessories to increase protection rating or extend functionality. These include
outlet filters in various designs,
absorber mats to increase protection rating to IP 55, and
spray water hoods for IP 56 protection. Additionally,
thermostats,
speed controllers, and
digital temperature display and control units are available to enable more precise ventilation control. Electrical connection is made via spring clamp terminals; for other models (3237.xxx), connection via individual wires is provided.
Mounting and Installation
Mounting is tool-free onto the enclosure wall. The installation depth is 84 mm, with the mounting cutout measuring 177 mm in width and height. The device dimensions are 204 mm width, 204 mm height, and 105 mm depth. The delivery includes a
front-side cover, which seals the fan after installation. Installation is quick and easy, requiring no tools.
Advantages in Operation
The operating temperature range is between -15 °C and 55 °C, with storage temperature up to 70 °C. The sound pressure level is 51 dB(A) at 50 Hz and 54 dB(A) at 60 Hz, ensuring quiet operation. The combination of diagonal fan technology and filtration ensures efficient and reliable climate control for the enclosure. Tool-free mounting and easy filter replacement reduce maintenance time and increase operational reliability. The IP 54 protection rating is standard, with higher protection levels achievable using additional components. Compatibility with various accessories allows flexible adaptation to different requirements in industrial applications.