| General |
| Model | Wall surface mounted |
| Material | Plastic |
| Colour | RAL 9005 |
| Scope of delivery | Outlet filter, pleated filter |
| Mounting cutout | Cutout width: 177 mm, cutout height: 177 mm |
| Suitable for part no. | SK 3239.7xx |
| Width | 204 mm |
| Height | 204 mm |
| Depth | 45,8 mm |
| NEMA degree of protection | Type 12 with felt filter/pleated filter, Type 3, 3R, 4, 4X with felt filter/pleated filter and spray water hood |
| Degree of protection IP according to IEC 60 529 | IP 54 with nonwoven filter/pleated filter, IP 55 with pleated filter and absorber mat, IP 56 with nonwoven filter/pleated filter and spray water hood |
The Rittal SK 3239.308 is an
outlet filter for filter fans of the SK 3239.7xx series, specifically designed for
enclosure climate control. It serves to dissipate waste heat from enclosures, ventilate the interior space, and protect temperature-sensitive components. The function is achieved by directly supplying ambient air, the temperature of which must be below the permissible enclosure internal temperature. The device is designed for
wall mounting and is made of
plastic in the colour
RAL 9005. Dimensions are 204 mm width, 204 mm height, and 45.8 mm depth, with the mounting cutout requiring a 177 mm width and 177 mm height opening.
Applications
The outlet filter is used in industrial installations where controlled ventilation and cooling of enclosures are required. It is particularly suitable for environments with increased dust or moisture exposure, as it can achieve various protection ratings in combination with appropriate filters. The device is used exclusively in conjunction with the filter fan SK 3239.7xx, creating a complete climate control solution.
Functions and Equipment in Detail
The filter features a new opening mechanism on the louver grille, which simplifies filter replacement. Mounting to the enclosure is tool-free and accelerated by optimised snap hooks. The delivery includes the outlet filter and a pleated filter. The filter components ensure efficient air purification and contribute to achieving the desired protection ratings.
Technology Explained Simply
Protection rating IP 54 is achieved when the filter is operated with a non-woven or pleated filter. For IP 55, an additional absorber mat is required, while IP 56 is achieved by combining a non-woven or pleated filter with a spray water hood. According to NEMA standards, the filter provides Type 12 protection with non-woven or pleated filter, and Type 3, 3R, 4, and 4X when used with an additional spray water hood. These protection ratings ensure effective protection against dust and splashing water, making it suitable for outdoor use or in moist industrial environments.
Compatibility and Accessories
The outlet filter is specifically designed for filter fans of the SK 3239.7xx series. Available accessories include replacement filter mats, spray water hoods made of stainless steel, absorber mats for IP 55, pleated filters for IP 55, and blanking covers for mounting cutouts. These components allow adaptation of the protection rating to specific environmental conditions and support maintenance and replacement of filter elements.
Mounting and Installation
Mounting is tool-free and can be quickly and securely performed on the enclosure using optimised snap hooks. A mounting cutout of 177 mm × 177 mm must be provided in the enclosure. The tool-free mounting reduces installation time and minimises the risk of mounting errors.
Advantages in Operation
The filter offers simple and quick maintenance thanks to the new opening mechanism on the louver grille. Tool-free mounting and rapid installation on the enclosure increase efficiency during commissioning and maintenance. The combination with various filter and protection components allows flexible adaptation to different operating conditions, thereby enhancing operational reliability and the service life of enclosure components.