| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 5.5 kW, Cooling capacity L35 L35/60 Hz: 5.5 kW, Cooling capacity L35 L50/50 Hz: 3.95 kW, Cooling capacity L35 L50/60 Hz: 3.95 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V), full installation not possible |
| Rated power | 2,35 kW |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity ratio L35 L35 (EER) 50 Hz: 2.5, cooling capacity ratio L35 L35 (EER) 60 Hz: 2.5 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,6 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 393 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-513A, quantity: 1.8 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 1.14 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 2.2 kW, Rated power L35 L35/60 Hz: 2.2 kW, Rated power L35 L50/50 Hz: 2.2 kW, Rated power L35 L50/60 Hz: 2.2 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 1.168,6 |
The Rittal SK 3189940 is a wall-mounted cooling unit of the Blue e+ series, designed for climate control of enclosures in semi-outdoor environments. It features a total cooling capacity of 5.5 kW at an operating voltage of 380 V to 480 V, 3~, 50 Hz/60 Hz. The unit is made of sheet steel and available in RAL 7035. Dimensions are 450 mm (width) × 1,600 mm (height) × 393 mm (depth), requiring a mounting cutout of 433 mm (width) × 1,579 mm (height). The cooling unit is not suitable for full enclosure installation.
Applications
This unit is designed for use in industrial environments, particularly in enclosures installed in semi-outdoor areas. Operating temperature ranges are between -20 °C and 60 °C, with the refrigerant circuit operating actively from 3 °C to 60 °C and the Heat Pipe from -20 °C to 45 °C. Storage temperature ranges extend from -40 °C to 70 °C. Temperature control is managed via an e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C.
Functions and Equipment in Detail
The cooling unit features a condenser with hydrophobic RiNano coating, making the surface water-repellent and increasing component lifespan. Integrated electric condensate evaporation ensures efficient removal of condensation. The unit is pre-wired with a plug-in terminal strip and includes mounting hardware. Airflow performance is 2,300 m³/h for both external and internal circuits. Rated power is 2.35 kW, nominal power is 2.2 kW. The refrigerant charge is 1.8 kg R-513A with a Global Warming Potential (GWP) of 631 and a CO₂ equivalent of 1.14 t.
Technology Explained Simply
Cooling capacity is measured according to DIN EN 14511. At an ambient temperature of 35 °C (L35), cooling capacity is 5.5 kW at 50 Hz and 60 Hz. At 50 °C (L50), cooling capacity is 3.95 kW at 50 Hz and 60 Hz. Energy efficiency is indicated by an Energy Efficiency Ratio (EER) of 2.5 at 50 Hz and 60 Hz, and a Seasonal Energy Efficiency Ratio (SEER) of 5.6. Variable-speed components and Heat Pipe technology enable an average energy saving of 75 %. The internal circuit protection rating is IP 55 according to EN 60 529, meaning dust-tight and splash-proof. The NEMA protection rating corresponds to UL Type 12 and UL Type 3R, suitable for industrial environments.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ cooling units, the IoT Interface with part number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages. Accessories include, among others, the SK condensate hose 12 x 2 mm (length 10 m), cover for the connection box (part number 3355.210), metal filters and filter mats for the specified SK models, and an air deflector for SK 3188. / 3189.xxx.
Installation and Mounting
The unit is designed for wall mounting and requires a mounting cutout of 433 mm (width) × 1,579 mm (height). Mounting is done using the included mounting hardware. The unit is pre-wired, simplifying installation. Operating voltage is between 380 V and 480 V, 3~, 50 Hz/60 Hz, with a tolerance of -10 % (342 V) at 380 V and +6 % (509 V) at 480 V. Appropriate overvoltage protection is required: for operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
Variable-speed components and Heat Pipe technology provide gentle component cooling, extending the lifespan of components in both the enclosure and the cooling unit. Integrated electric condensate evaporation reduces maintenance effort. Intuitive operation is provided via the e+ controller. Multi-voltage capability enables worldwide use. Remote monitoring via the IoT Interface increases machine availability and process reliability. Refrigerant R-513A has a lower Global Warming Potential compared to older refrigerants.