| General |
| Model | Wall mounting, chemical industry |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Applications | Applications where sulfuric acid may be present as an aerosol in the air (e.g. paper industry, food industry, chemical industry, electroplating, offshore area) |
| Material | steel sheet |
| Surface protection | Sheet metal parts and electronics coated with clear lacquer, refrigeration circuit coated with 2K PUR lacquer |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1.6 kW, cooling capacity L35 L35/60 Hz: 1.6 kW, cooling capacity L35 L50/50 Hz: 1.2 kW, cooling capacity L35 L50/60 Hz: 1.2 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,7 kW |
| Air performance (free blowing) | External circuit: 895 m³/h, Internal circuit: 700 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.96, Cooling performance factor L35 L35 (EER) 60 Hz: 2.96 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,5 |
| Width | 400 mm |
| Height | 950 mm |
| Depth | 310 mm |
| Required mounting cutout | Cutout width: 383 mm, cutout height: 929 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| Refrigerant/cooling medium | Refrigerant: R-513A, quantity: 0.76 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 0.48 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.54 kW, rated power L35 L35/60 Hz: 0.54 kW, rated power L35 L50/50 Hz: 0.61 kW, rated power L35 L50/60 Hz: 0.61 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 660,04 |
The Rittal SK 3185835 is a wall-mounted cooling unit of the Blue e+ Chemistry series, specifically designed for use in environments where sulfuric acid may be present as an aerosol in the air. This includes applications in the paper industry, food industry, chemical industry, galvanizing, or offshore environments. The unit is made of sheet metal and features a special surface coating: sheet metal parts and electronics are coated with clear lacquer, while the refrigeration circuit is coated with a 2-component PUR lacquer to enhance corrosion resistance. The unit's color corresponds to RAL 7035. Dimensions are 400 mm (width) × 950 mm (height) × 310 mm (depth), requiring a mounting cutout of 383 mm (width) × 929 mm (height). The cooling unit is intended for semi-outdoor use and must not be used in open, unprotected outdoor areas.
Applications
This cooling unit is designed for industrial applications where aggressive environmental conditions such as acidic aerosols prevail. The special chemistry version ensures high corrosion resistance and extends the service life of components in the enclosure as well as the cooling unit itself. Operating limits are defined by an ambient temperature range of -20 °C to 60 °C, with the refrigerant circuit operating between 3 °C and 60 °C during active operation and the heat pipe operating between -20 °C and 45 °C. Storage temperature ranges from -40 °C to 70 °C.
Functions and Equipment in Detail
The unit features an integrated condenser with hydrophobic RiNano coating, which reduces condensation formation and simplifies maintenance. The integrated electric condensate evaporation ensures that the condensate produced evaporates directly within the unit, eliminating the need for an external drain. Temperature control is managed by an e+ controller, factory-set to +35 °C, with an adjustable range between 20 °C and 50 °C. The unit is pre-wired and includes a plug-in terminal strip. Mounting materials are included in the delivery scope.
Technology Explained Simply
The cooling unit operates with refrigerant R-513A, with a quantity of 0.76 kg. The Global Warming Potential (GWP) is 631, equivalent to 0.48 t of CO₂. The total cooling capacity is 1.6 kW at an ambient temperature of 35 °C (L35) and operating voltage of 110–240 V (1~) or 380–480 V (3~) at 50/60 Hz. At an ambient temperature of 50 °C (L50), the cooling capacity is 1.2 kW. The rated power is 0.7 kW. Airflow in the external circuit is 895 m³/h, and in the internal circuit, 700 m³/h. Energy efficiency is characterized by an Energy Efficiency Ratio (EER) of 2.96 (at 50/60 Hz, L35) and a Seasonal Energy Efficiency Ratio (SEER) of 5.5. The operating voltage includes 110–240 V, 1~, 50/60 Hz, and 380–480 V, 3~, 50/60 Hz. The permissible voltage tolerance is -10 % (99 V) at 110 V and +10 % (264 V) at 240 V, -10 % (342 V) at 380 V and +6 % (509 V) at 480 V. The permissible operating pressure is 24 bar. The protection rating of the internal circuit corresponds to IP 55 according to EN 60 529, meaning dust-tight and splash-proof.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ generation cooling units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to increase machine availability and process safety. Available accessories include, among others, covers for the connection box (article numbers 3355.200 and 3355.210), a condensate hose (12 x 2 mm, length 10 m), an air deflector for SK 3185.xxx, a temperature sensor for Blue e+ cooling units, and a metal filter for SK 3185830.
Mounting and Installation
The unit is designed for wall mounting and requires a mounting cutout of 383 mm (width) × 929 mm (height). Mounting materials are included in the delivery scope. The terminal strip is plug-in, so the unit is pre-wired. For protection of the cooling unit, an appropriate surge protection device must be provided: for operating voltages below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
The variable-speed components and heat pipe technology ensure an average energy saving of 75 %. The gentle component cooling extends the service life of components in the enclosure and in the cooling unit. Intuitive operation is provided via a touch display and intelligent interfaces. Multi-voltage capability enables worldwide use without rewiring. The integrated condensate evaporation reduces maintenance effort, as no external drain is required.