| Technical data |
| Shape | Angular |
| Dimensions (W x H) | 220 x 220 mm |
| Sound pressure level (SPL) 1 W/1 m | 95 dB |
| Built-in depth | 70 mm |
| Adjustments at 100 V | 2x 6/3/1,5 W |
| Impedance | 8 Ohm |
| Sound pressure level (SPL) Pmax/1 m | 111,2 dB @182Hz |
| Colour | White |
| Cutout (W x H) | 187 x 187 mm, (±5mm) |
| Beam angle (-6dB, 1 kHz) | 180° |
| Rated load capacity (program) | 2x 6 W (15 W) |
| Frequency range (±10dB) | 90 – 16.000 Hz |
| Speaker | 2 St. 4" x 2,5" |
The SC-512 EN-1 from RCS Audio-Systems is a certified
ceiling-mounted loudspeaker for
voice alarm systems in accordance with the standard
EN 54-24:2008. It is specifically designed for applications with high safety requirements, where redundant sound coverage is necessary. The integrated
dual configuration with two loudspeakers and two transformers enables a true A/B split, as required by DIN EN 60849 / VDE 0828 and VDE 0833-4. This ensures that alarm signaling can continue even if one channel fails, thereby increasing system reliability.
Applications
This loudspeaker is suitable for use in buildings with fire protection requirements, such as office buildings, hotels, hospitals, or public facilities. Certification according to EN 54-24:2008 ensures compliance with European safety standards for alarm devices. The design is intended for flush installation in ceilings, with a discreet edge height of approximately 2 mm enabling unobtrusive integration into architectural design.
Functions and Features in Detail
The SC-512 EN-1 features two
10,2 cm ( 4 inch ) x 6,3 cm ( 2,5 inch ) oval wideband chassis with tweeter cones, ensuring clear and balanced sound. The
rated power handling is 2 x 6 W (program power), with maximum power reaching up to 15 W. The
sound pressure levels are 95 dB at 1 W/1 m and 111.2 dB at maximum power (Pmax/1 m), providing sufficient loudness for alarm functions. The
frequency range covers 90 to 16,000 Hz (±10 dB), enabling clear voice reproduction. The
radiation angle is 180° (-6 dB at 1 kHz), ensuring even coverage of the room.
Technology Explained Simply
The loudspeakers are designed for operation in a 100-V amplifier system, with power taps including 2 x 6 W, 3 W, and 1.5 W. The impedance is 8 Ohm, allowing compatible connection to standard amplifiers. The housing is made of
impact-, shock-, and fire-resistant ABS plastic (UL94V0), providing high mechanical and thermal stability. A coated steel perforated sheet ensures
theft-resistant construction. The integrated
cover hood protects against dripping water, enabling use in areas with increased humidity.
Compatibility and Accessories
The loudspeaker is designed for use in
100-V amplifier systems. An optional
humid environment version is available, equipped with treated chassis and transformers to meet requirements in humid rooms.
Special lacquering in RAL colors is available upon request, allowing adaptation to room design.
Installation and Mounting
Installation is performed using a
quick-tension system, enabling easy and secure mounting even in plasterboard ceilings. The
cutout size is 187 x 187 mm (±5 mm), while the external dimensions are 220 x 220 mm.
Operational Advantages
The combination of
EN 54-24:2008 certification,
A/B redundancy,
robust housing, and
easy installation makes the SC-512 EN-1 a reliable solution for fire protection and voice alarm systems. The integrated cover hood and the option for a humid environment version extend the range of applications. The discreet appearance and low edge height ensure unobtrusive integration into ceiling structures.