RCS Audio-Systems PHM-802 C, EAN: 4250458235301

RCS Audio-Systems PHM-802 C amplifier monitoring 1 HE digital

100V Electro Acoustic Systems > Emergency warning systems

RCS Audio-Systems PHM-802 C amplifier monitoring 1 HE digital

Lieske Part No. 102316
Mfg Part No PHM-802 C
EAN-Code 4250458235301
Manufacturer RCS Audio-Systems
Here only 1.320,50 EUR
1.571,40 EUR incl. VAT

Further information for RCS Audio-Systems PHM-802 C amplifier monitoring 1 HE digital

Technical data
Power supply24 V DC
Measurement intervalAdjustable 15/30/45/60/90 sec. (5 sec. with bus option)
Listening powerOutput stage 1.3W RMS
Switching power6 A per channel
InterfacesRS485 bus (optional) on RJ-45, fault alarm output, RS232 for firmware update
Dimensions (W x H x D)483 x 44 x 171 mm; 1 HE
Power consumption5 W
Height units1 HE
IndicationLCD Dot Matrix 2x24, backlit, contrast adjustable
Power suppliesswitching power supply / battery (emergency power supply 24 V)
Monitored amplifiers8 + 1 (emergency) or 2x 4 + 2x 1 (emergency)
System compatibilityVARES-3000
Pilot tone19/19.5/20/20.5/21/21.5/22/22.5/23/23.5/24/24.5/25 kHz
19" rack mountingJa
The PHM-802C from RCS Audio-Systems is a digital fault management system for the continuous monitoring of up to 10 amplifiers in voice alarm systems. It is designed for continuous functional control of call amplifiers and fault amplifiers, automatically switching to a backup amplifier in case of failure. The device is designed for use in emergency warning systems and operates both independently and integrated into the VARES-3000 system. Monitoring is performed via a pilot tone, available in a frequency range of 19 to 25 kHz and individually adjustable for each respective 100V output stage. The status display is provided by an LCD Dot Matrix 2x24 display, which is illuminated and equipped with adjustable contrast control, enabling the status of each individual amplifier to be clearly visible.

Applications

The PHM-802C is intended for use in professional sound systems, particularly in buildings with emergency warning systems such as hospitals, administrative buildings, or public facilities. It ensures the reliability of voice alarm systems by detecting faults in amplifiers and responding accordingly. Configuration is performed via a self-explanatory menu with four buttons on the front panel, eliminating the need for additional software or a computer for commissioning. Fault messages are displayed until the error is resolved, enabling quick fault localization.

Functions and Equipment in Detail

The device monitors up to 8 call amplifiers and 2 fault amplifiers. Configuration is flexible: either all 8 amplifiers assigned to one fault amplifier, or two groups of 4 amplifiers each, each with its own fault amplifier. Operation without fault amplifiers is also possible. The measurement intervals are adjustable (15, 30, 45, 60, 90 seconds), with an optional bus option allowing for a 5-second interval. The switching capacity is 6 A per channel, sufficient to safely switch the amplifiers. The monitoring power of the integrated amplifier stage is 1.3 W RMS, sufficient to monitor the amplifier outputs via a speaker.

Technology Explained Simply

The operation is based on periodic querying of the amplifiers via a pilot tone, set to the respective frequency range. If an amplifier does not correctly reproduce the pilot tone, a fault is detected and the device automatically switches to the fault amplifier. The power supply is 24 V DC, with the device designed for operation with a switching power supply (230 V AC → 24 V DC) and includes an additional emergency power input for 24 V DC to ensure continued operation during a power failure. The power consumption is 5 W, ensuring efficient energy use.

Compatibility and Accessories

The PHM-802C is part of the VARES-3000 system and can be integrated into the system via an optional RS485 bus interface (PHM-485 B). This enables central monitoring and configuration via the ConfigV7620 cm ( 3000 inch ) software. Optionally, the monitor module PMU-802A can be installed to monitor all 10 amplifier outputs. Channel selection and volume control can be managed via the device buttons or via a connected PC using the "ConfigV3000 software.

Mounting and Installation

The device is designed for 48,3 cm ( 19 inch ) rack mounting and occupies 1 HE (height unit). Dimensions are 483 x 44 x 171 mm (W x H x D). All connections are equipped with screw connectors, suitable for secure and user-friendly installation. Installation requires no additional tools or special expertise, as operation is performed via the menu and buttons.

Operational Advantages

The PHM-802C offers high operational reliability through automatic fault detection and correction. The clear display of status messages on the screen enables quick diagnosis. The ability to combine multiple PHM-802C devices expands monitoring capacity. Integration into the VARES-3000 system enables central control and monitoring, simplifying maintenance and configuration. The emergency power supply ensures continued functionality during power outages, which is critical for emergency warning systems. Batteries are not included in the delivery scope.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/102316
qrcode für RCS Audio-Systems PHM-802 C amplifier monitoring 1 HE digital