| General |
| Device type | safety switchgear |
| Operation mode | Standalone |
| Inputs | 1/2-channel wiring with/without cross-connection detection |
| Outputs | 2 S |
| Start function | Automatic/manual/supervised start |
| Operating voltage | 24 V AC/DC |
| Connection type | Screw terminals, plug-in type |
| Monitoring functions | Emergency stop, safety doors |
The safety control device PNOZX2P24VAC/DC2N/O from Pilz is a standalone system for the safe control of machines and plants. It is used for monitoring emergency stop functions and safety doors and enables the safe disconnection of drives and power supplies in the event of a fault. The device is designed for use in industrial environments, where compliance with safety standards and the reliability of control components are of critical importance.
Applications
The device is used in plants where safe disconnection in the event of a fault is required, for example in the manufacturing industry, with presses, robot systems or in packaging technology. It monitors the function of emergency stop switches and safety doors to ensure that the machine can only be started when all safety conditions are met. The 1- or 2-channel wiring allows flexible adaptation to different safety requirements.
Functions and equipment in detail
The device features two safe outputs (2 S), which can be used to control drives or other safety-relevant components. The start function can be set in three variants: automatic, manual, or monitored. Cross-circuit detection can be optionally activated to monitor the integrity of safety wiring. The plug-in screw terminals facilitate installation and maintenance, as they allow quick and secure connection of the wires.
Technology explained simply
The device operates with a supply voltage of 24 V AC/DC, making it suitable for a wide range of industrial applications. The width of 22.5 mm allows for compact mounting in standard control panels. The monitoring functions ensure that the machine can only be started when all safety conditions are met. The integrated cross-circuit detection recognizes if a wire is broken or short-circuited, thus preventing dangerous conditions.
Compatibility and accessories
For use with the device, the accessory PNOZXSETPLUGINSCREWTERMINALSP1+P2 is available, which provides additional plug-in screw terminals for connections P1 and P2. These expand the connection options and facilitate installation, especially in complex systems with many connections.
Mounting and installation
The device is mounted in standard control panels, with the width of 22.5 mm enabling compact placement. The plug-in screw terminals simplify wiring, as they can be mounted and removed without tools. Installation is carried out in accordance with the technical requirements of safety standards, ensuring correct wiring of inputs and outputs.
Advantages in operation
The combination of compact design, flexible configuration and integrated monitoring functions makes the device a reliable solution for industrial safety technology. The simple mounting and maintenance via plug-in screw terminals reduces installation time and facilitates maintenance. The support for various start types allows adaptation to different operational requirements.