Further information for OBO Bettermann MCF100-3+NPE+FS (5096987)
Combined arrester, lightning current and surge arrester type 1+2
. Protection level = 1.5 kV
. for lightning protection equipotential bonding in accordance with VDE 0185-305 (IEC 62305)
. Lightning current discharge capacity up to 100 kA (10/350) 3+NPE
. Mains follow current extinguishing 50 kA Ipeak, arrester backup fuse up to 315 A gL/gG
. Meets the requirements of VDE-AR-N 4100 for use in the pre-meter area
. Encapsulated non-blow-out spark gap arresters for use in distribution boxes
Application: Industrial plants and buildings with external lightning protection of classes I to IV.