Further information for OBO Bettermann MCD 50-B - lightning arresters 1 pole 255 volt complete
Combined arrester type 1+2 for use in TN and TT networks
. Lightning protection equipotential bonding in accordance with VDE 0185-305 (IEC 62305)
. Lightning current discharge capacity 50 kA (10/350) per pole and up to 150 kA (10/350) in total
. Protection level <1.7 kV, enables device protection
. Short-circuit strength 10 kA, arrester backup fuse up to 500 A gL/gG
. Encapsulated, non-blow-out spark gaps
. Application: Industrial plants and buildings with external lightning protection of classes I to IV.