Further information for Niedax 4013339952366 - KKL 110 300 KKL110 300 Kabelr 110x300x3000mmangeformtem verb Gel
GRP cable tray, pressed, with unperforated side rails and molded connector, with transverse reinforcements (5 mm) over the entire width of the cable tray and eleven-row fastening holes in the base, mechanical strength in accordance with IEC 61537, please order appropriate fastening accessories separately, halogen-free. Due to the transverse reinforcements, the cable tray is also approved for use with high-frequency cables in accordance with UTE C15-900 (application class D, frequency 16 MHz). An expansion distance of 8 mm must be taken into account. Due to the expansion of the material, the following must be observed during assembly: - The cable tray should not be screwed close to or at the joint. - When screwing the cable tray onto the brackets, a through hole of Ø 9 mm for the FKM 6X20 E4 screws must always be made in the tray. Article also available in ...AC (resin mixture with acrylic resin). Dimensions (approx. dimensions) H x W : 110 x 300 mm Material thickness t : 4 mm Bottom bead shape : 60 x 5 mm Bottom bead shape Grid dimension : 250 mm Bottom perforation : 9 x 20 mm Row spacing : 25 mm Bottom hole spacing Grid dimension : 250 mm Load capacity F at a support spacing of 1.5 m : 1.2 kN/m Delivery length : 3000 mm Usable cross-section : 28356 mm² Material : UP-GF (glass fiber reinforced polyester) Color : pebble gray RAL : 7032 (similar)