| Weight & dimensions |
| Weight | 15000 g |
| Dimensions (W x D x H) | 25.85 x 25.88 x 16 " |
| Dimensions (WxDxH) | 657 x 657 x 406 mm |
| Technical details |
| Compatible products | C925, X925 |
| Packaging data |
| Package dimensions (W x D x H) | 27.6 x 25.5 x 16.9 " |
| Package weight | 18100 g |
| Package dimensions (WxDxH) | 701 x 648 x 429 mm |
Frequency converter, type code: DC1, rated operating voltage: Ue = 230 V AC, 1-phase, 240 V AC, 1-phase, output voltage at Ue: U2 = 230 V AC, 1-phase, 240 V AC, 1-phase, mains voltage (50/60Hz): ULN = 200 (-10%) - 240 (+10%) V, rated operating current at 150% overload: Ie = 4.3 A, note: rated operating current at a switching frequency of 6 kHz and an ambient temperature of +40 °C, note: overload cycle for 60 s every 600 s, assigned motor power note: for internally and externally ventilated AC motors with 50/60 Hz without additional starting capacitor, overload cycle for 60 s every 600 s, at 230 V, 50 Hz, Assigned motor power 150% overload: P = 0.37 kW, 150% overload: IM = 4.3 A, Assigned motor power note: at 220 - 240 V, 60 Hz, Assigned motor power 150% overload: P = 0.5 HP, Assigned motor power 150% overload: IM = 4.3 A, Protection class: IP66/NEMA 4X, Interface/fieldbus (built-in): OP-Bus (RS485)/Modbus RTU, CANopen®, Fieldbus connection (optional): SmartWire-DT, Equipment: Radio interference filter, 7-segment display, Local controls, additional circuit board protection, UV-resistant, Size: FS1, Standards and regulations: General requirements: IEC/EN 61800-2, EMC requirements: IEC/EN 61800-3, Safety requirements: IEC/EN 61800-5-1