| General |
| Conveying volume | 200 m3/h |
| Rotational speed | 1672 1/min |
| Nominal power | 15 W |
| Rated voltage | 230 V |
| Mains frequency | 50 Hz |
| IMax | 0,09 A |
| Degree of protection | IP X5 |
| Mains supply cable | 5 x 1.5 mm2 |
| Mounting position | Ceiling / Wall |
| Mounting type | Surface mounted (plaster) |
| Built-in position | Any |
| Material | Plastic |
| Colour | traffic white, similar to RAL 9016 |
| Nominal width | 150 mm |
| Conveyor temperature at IMax | 40 °C |
| Response time | 0 min |
| Switching-on delay | 0 s |
| Sound pressure level | 33 dB(A) |
| SEC average | -11,04 kWh/(m2*a) |
The Maico ECA 150 ipro VZC is a two-stage small-room fan, specifically designed for ventilation in bathrooms and other humid rooms. It features an adjustable switch-on delay and run-down time, which can be set via easily accessible buttons on the device. These functions allow for flexible adaptation to different usage scenarios, with the set times displayed during configuration via LEDs. The fan is not speed-controlled and offers two performance stages with a flow rate of 200 m³/h and 250 m³/h. The speeds are 1672 1/min and 2189 1/min, with rated power of 15 W and 19 W respectively. The operating voltage is 230 V AC at a network frequency of 50 Hz. The maximum current draw is 0.09 A. The fan is designed for continuous operation and includes a thermal overload protection, ensuring safety during operation.
Applications
The fan is suitable for ventilation in rooms with high humidity such as bathrooms, shower rooms, or kitchens. It can be used in protection zone 1 according to DIN VDE 0100-701, ensuring safe use in humid environments. The protection class IP X5 ensures protection against splashing water, making it suitable for use in bathroom areas. The traffic white color, similar to RAL 9016, ensures unobtrusive integration into room design. The housing is made of impact-resistant plastic, ensuring high mechanical stability and durability.
Functions and Equipment in Detail
The ECA 150 ipro VZC offers four different operating programs, which can be selected via jumpers inside the device: Comfort program (pre-set), Demand program, Saving program, and Power program. Depending on the program, the sequence of performance stages during user presence and during run-down time varies. The switch-on delay can be set in steps of 0, 50, 90, or 120 seconds, and the run-down time in steps of 0, 8, 17, or 25 minutes. Control is via a light switch or a separate switch. The concealed intake through a design cover ensures an aesthetic appearance.
Technology Explained Simply
The fan operates with an energy-saving, maintenance-free motor with ball bearings, designed for continuous operation. Protection class II ensures high safety without the need for a protective earth connection. The mains supply cable has a cross-section of 5 × 1.5 mm². The performance is measured at a medium temperature of 40 °C. The sound pressure levels are 33 dB(A) and 40 dB(A) at a distance of 3 m under free-field conditions, indicating quiet operation. The device is designed for any installation orientation, allowing both wall and ceiling mounting.
Compatibility and Accessories
The fan is compatible with predecessor models of the ECA series DN 150, as the mounting holes and cable entry for in-wall installation are in the same position. The installation method is optionally surface or in-wall. The nominal size is 150 mm. The device dimensions are 228 mm (width) × 228 mm (height) × 123.3 mm (depth). The weight is 1.6 kg. The SEC average is -11.04 kWh/(m²*a), indicating energy-efficient use.
Installation and Mounting
Installation is carried out on the ceiling or wall, with mounting holes and cable entry compatible with predecessor models. The electrical connection can be made either surface or in-wall. The installation orientation is arbitrary, allowing flexible installation. The maximum medium temperature at IMax is 40 °C.
Operational Advantages
The fan combines high flow volume with high pressure strength, enabling efficient ventilation even in larger rooms. The adjustable switch-on delay and run-down time ensure optimized use, with operating programs selectable according to requirements. The maintenance-free design and thermal overload protection increase operational safety. The VDE GS mark confirms safety compliance. The quiet operation with sound pressure levels of 33 dB(A) and 40 dB(A) ensures disturbance-free use.