LTC

LTC H07V-K 50,0 SW TR Cable 50,0 mm² black

Cables > Installation systems and industrial management > Wiring cable H05 / 07V-K

LTC H07V-K 50,0 SW TR Cable 50,0 mm² black

Lieske Part No. 695292
Mfg Part No
EAN-Code
Manufacturer LTC
Here only 14,21 EUR
16,91 EUR incl. VAT

Further information for LTC H07V-K 50,0 SW TR Cable 50,0 mm² black

General
Nominal voltage450/750 V
Test voltage2500 V
Installation temperature range+5 °C - +70 °C
Temperature range after installation-30 °C - +70 °C
Operation temperature+70 °C
Bending radius15 x cable diameter
Flame retardancyAccording to VDE 0472 T. 804 test type B (IEC 332-1)
Conductorbare copper, fine-stranded
InsulationPVC according to VDE 0207
Sheath colourin accordance with VDE 0293
The PVC-insulated single-core cable H07V-K 50,0 SW TR from LTC is an installation cable designed for use in dry rooms, particularly in control and distribution systems. It is suitable for installation in conduits, both above and below plaster, as well as in closed installation channels. The cable is used for internal wiring of devices, control panels, and distributors, and is also intended for protected installation in and on luminaires. The maximum rated voltage is 1000 V AC or 750 V DC to earth. Direct installation on trays, troughs, or channels is not intended.

Applications
This cable is designed for indoor use where a dry environment is guaranteed. It is commonly used in electrical installations requiring fixed and permanent wiring, such as in residential and commercial buildings. Its use in devices, control panels, and distributors enables safe and reliable power supply. The cable is not suitable for outdoor use or in damp areas, as it does not offer special protection against moisture or mechanical stress.

Functions and Features in Detail
The single-core cable consists of a bare, fine-stranded copper conductor, ensuring high electrical conductivity. The insulation is made of PVC, specified according to VDE 0207, providing high mechanical and thermal resistance. The sheath color complies with the requirements of standard VDE 0293, ensuring uniform color coding in electrical installations. The cable is designed for a maximum operating temperature of +70 °C, enabling stable performance under normal operating conditions.

Technical Explanation
The rated voltage of 450/750 V defines the maximum voltage the cable can safely transmit. The test voltage of 2500 V serves as a safety margin, ensuring the insulation does not break down even under increased stress. Temperature ranges are defined in two phases: during installation, the range is between +5 °C and +70 °C; after installation, the cable can be operated at temperatures from -30 °C to +70 °C. The minimum bending radius is 15 times the cable diameter, allowing safe bending without damaging the conductor. Flame retardancy according to VDE 0472 T. 804 test method B (equivalent to IEC 332-1) ensures the cable does not ignite quickly in case of fire and limits flame spread.

Compatibility and Accessories
The cable is designed for standard installations and can be installed using common installation techniques. It is compatible with standard terminals, plug connectors, and other connection elements designed for PVC-insulated cables. The use of protective conduits or installation channels is recommended to protect the cable from mechanical damage.

Installation and Mounting
Installation is carried out by routing the cable in conduits or closed channels. The cable must maintain a bending radius of at least 15 times its diameter to avoid damaging the copper conductor. Installation takes place in dry rooms, with ambient temperatures during installation ranging from +5 °C to +70 °C. After installation, the cable can be operated at temperatures from -30 °C to +70 °C. Connections are made using appropriate terminals or plug connectors designed for a conductor cross-section of 50.0 mm².

Operational Advantages
The cable offers high electrical conductivity due to the bare, fine-stranded copper conductor. The PVC insulation ensures high mechanical and thermal resistance. Flame retardancy according to VDE 0472 T. 804 test method B enhances safety in case of fire. Uniform color coding according to VDE 0293 simplifies identification and maintenance of the cable. The maximum operating temperature of +70 °C enables stable operation under normal environmental conditions.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/695292
qrcode für LTC H07V-K 50,0 SW TR Cable 50,0 mm² black