| General |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Operation temperature | +70 °C |
| Bending radius | 15 x cable diameter |
| Flame retardancy | according to VDE 0472 T. 804 test type B (=IEC 332-1) |
| Conductor | bare copper, fine-stranded |
| Insulation | PVC according to VDE 0207 |
| Sheath colour | dark blue RAL 5010 |
| Application | internal wiring of devices, protected installation in luminaires, conduits, on and under plaster, only for doorbell and signaling systems |
The H05V-K 0.5 DBL RAL 5010 is a flexible PVC wiring cable from manufacturer LTC, designed specifically for internal wiring of devices as well as for protected installations in and on luminaires, in conduits, on and under plaster. The cable is suitable exclusively for applications in bell and signaling systems. It features a bare, fine-stranded copper conductor and PVC insulation manufactured in accordance with VDE 0207. The sheath color complies with standard VDE 0293 and is executed in dark blue (RAL 5010), enabling clear identification in wiring applications.
Applications
This cable is designed for use in protected indoor environments, for example in electrical installations of devices, in lighting systems, or in conduit systems. It must not be used for main power supplies or for applications with higher voltages, but is exclusively intended for signal circuits such as bell systems or alarm systems. Installation must consider the specified temperature and bending conditions.
Functions and Features in Detail
The conductor is made of bare, fine-stranded copper, ensuring high flexibility and good electrical conductivity. The PVC insulation provides sufficient electrical protection and is specified according to VDE 0207. The dark blue sheath color (RAL 5010) serves visual differentiation and complies with standard VDE 0293. The cable is rated for a nominal voltage of 300/500 V, which is sufficient for most signaling applications. The test voltage is 2000 V, highlighting its electrical strength.
Technical Explanation
The maximum operating temperature is +70 °C, and the cable may be installed during installation at temperatures between +5 °C and +70 °C. After installation, an operating temperature range of -30 °C to +70 °C is permissible, allowing use in indoor environments with varying climatic conditions. The minimum bending radius is 15 times the cable diameter, ensuring flexible installation without mechanical damage. Flame retardancy corresponds to test method B according to VDE 0472 T. 804 (equivalent to IEC 332-1), meaning the cable does not propagate flame during a fire test and thus presents limited fire hazard.
Compatibility and Accessories
The cable is designed for use in signaling systems and can be connected to other components such as bell push buttons, signal transmitters, or relays. Connections are made using suitable connectors or terminals rated for the nominal voltage and cross-section.
Installation and Mounting
Installation must consider the specified temperature and bending conditions. The cable must not be excessively bent or stretched to avoid mechanical damage. Installation takes place in protected areas, for example in conduits, under plaster, or in luminaires. Connection techniques use appropriate terminals or connectors rated for the nominal voltage and cross-section.
Operational Advantages
The cable offers high flexibility due to the fine-stranded copper conductor, enabling easy installation in confined spaces. The PVC insulation ensures sufficient electrical insulation, and flame retardancy according to VDE 0472 T. 804 (test method B) increases safety in case of fire. The dark blue color (RAL 5010) facilitates identification in wiring applications. The cable is specifically designed for signaling systems, enabling clear assignment to specific application areas.