Further information for JUNG FMES36804REG - radio Energiesenso 4 channel REG
New system function: fully encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
Intended use
Energy sensor for determining energy values
Sensor for load-dependent control of eNet actuators with eNet server
Transmission of measured values to the eNet server
Operation with power supply 12 V REG (item no. NT 1220 REG VDC) and eNet radio receiver module REG (item no. FM FK 32 REG) or eNet server
Installation on top hat rail according to DIN EN 60715 in sub-distribution board
Product features
Calculation of the active power and active energy separately for each measuring channel
Event- or time-controlled sending of measured value telegrams to the eNet server
Fully encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
Update of the device software
Nominal voltage: AC 230 V ~, 50/60 Hz
Nominal load current: 16 A
Peak current (1 s): 80 A
Peak current (1 min): 24 A
Power consumption per channel: 225 mW
Ambient temperature: ?5 ... +45 °C
Transmission interval: 1 ... 60 min
Load terminal connection: screw terminals,
single-wire: 1 x 1.5 ... 4 mm2,
fine-wire without ferrule: 1 x 0.75 ... 4 mm2,
fine-wire with ferrule: 1 x 0.5 ... 2.5 mm2
Installation width: 72 mm (4 HP)
Bus cable
Nominal voltage: DC 12 V SELV
Current consumption: 10 mA
Bus connection: connection terminal
Cable length: max. 3 m
Measuring ranges per channel
Current: 0 mA ... 16 A
Accuracy (current): ± 0.5 % of the current value and ± 8 mA
Voltage: 207 ... 250 V
Accuracy (voltage): ± 0.5 % of the current Value
Transmitted power and energy values
Active power: ?4,000 ... 4,000 W
Apparent power: 0 ... 4,000 VA
Reactive power: ?4,000 ... 4,000 var
Accuracy (power): ± 0.5 % of the current value and ± 2 W/VA/var
Active energy: ?99,999 ... 99,999 kWh