| General |
| Rated operating voltage | 800 V AC |
| Rated operation current | 160 A |
| Conventional thermal current rating | 160 A |
| Rated frequency | 50-60 Hz |
| Rated insulation voltage | 800 V AC |
| Rated surge voltage | 8 kV |
| Short-circuit withstand capability | 60 kA |
| Total power loss at Ith | 23 W |
| Maximum permissible power loss per fuse carrier | 12 W |
| Degree of protection (operational) | IP30 |
| Degree of protection (cover open) | IP10 |
| Ambient temperature | -25 to +70 °C |
| Operation mode | Continuous operation |
| Connection type | flat connection |
| Bolt diameter | M8 |
| Cable cross-section | 1 x 10-95 mm² |
| Utility category | AC-22B (125A/800V) |
| Fuse type | NH fuse according to DIN VDE 0636-2 |
| Busbar system | 185 mm |
The article
Jean Müller SL00-3X3/185/F (manufacturer number L5061001) is an
NH fuse switch disconnector for use in electrical distribution systems with a rated operational voltage of
800 V AC. It is specifically designed for installation in
185 mm busbar systems and enables safe load disconnection and switching under load, with the integrated NH fuse protection function safeguarding against overloads and short circuits. The construction is designed for use in industrial and commercial installations where high operational safety and reliability are required.
Applications
The switch disconnector is used in distribution systems where electrical load disconnection is required, for example in machine controls, drive systems, or in building electrotechnics. It is suitable for use in
AC-22B applications (125 A / 800 V), allowing use in installations with high thermal and electrical loads. The switching devices are intended for use in
indoor installations, with a protection rating of IP30 in the operational state. When the switch cover is open, the protection rating drops to IP10, allowing access to internal contacts, but no longer providing protection against contact or foreign objects.
Functions and Equipment in Detail
The switch features a
flat connection with a bolt diameter of
M8, designed for cable lugs according to DIN 46 235. The permissible cross-sectional area is
1 x 10–95 mm², with a maximum lug width of 25 mm. The rated operating current is
160 A, with the conventional thermal current-carrying capacity in air with fuses also being 160 A. The rated frequency is specified for
50–60 Hz, enabling use in European and international networks. The total power loss under thermal load is
23 W, with the maximum permissible power loss per fuse insert being
12 W.
Technology Explained Simply
The switch disconnector is equipped with an
NH fuse according to DIN VDE 0636-2, which automatically interrupts the circuit in the event of a short circuit or overload. The fuse protection function is realized through the integrated fuse holder, designed for mounting NH fuses. The short-circuit current withstand capability is
60 kA, ensuring high safety against sudden current surges. The rated insulation voltage is
800 V AC, ensuring electrical insulation between conductors and the housing. The rated impulse voltage is
8 kV, describing the device’s ability to withstand short-term voltage spikes.
Compatibility and Accessories
The switch is specifically designed for
185 mm busbar systems and can be mounted directly in these systems. The cable connection variant is a flat connection with M8 bolts, suitable for cable lugs with a cross-section of 10 to 95 mm². The use of NH fuses according to DIN VDE 0636-2 is required to ensure the protection function.
Mounting and Installation
Mounting is done into the 185 mm busbar system, with cable connections possible at the top or bottom. Operation is manual, with hand operation depending on the switch position. The ambient temperature for operation ranges from
–25 °C to +70 °C, enabling use in a wide range of environments. The operating mode is defined as
continuous duty, meaning the device can be operated continuously under load.
Advantages in Operation
The switch disconnector offers high operational safety through the integrated NH fuse, protecting against overloads and short circuits. The construction allows for easy mounting in 185 mm busbar systems and safe load disconnection under load. The high short-circuit current withstand capability of 60 kA ensures reliable protection. The IP30 protection rating in the operational state provides protection against contact and foreign objects, increasing safety during operation. The rating for 800 V AC makes the switch suitable for applications in high-voltage networks, which are common in industry and commerce.