Hager NBN116, EAN: 3250614613722

Hager NBN116 Circuit Breaker 1P B-16A

Installation > Modular devices / equipment installation > Circuit breaker

Hager NBN116 Circuit Breaker 1P B-16A

Lieske Part No. 506384
Mfg Part No NBN116
EAN-Code 3250614613722
Manufacturer Hager
Here only 26,79 EUR
31,88 EUR incl. VAT

Further information for Hager NBN116 Circuit Breaker 1P B-16A

General
Release characteristicB
Number of poles (total)1
Number of protected poles1
Rated current16 A
Rated voltage400 V
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp6 kV
Rated short-circuit breaking capacity Icn EN 60898 at 230 V10 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V15 kA
Voltage typeAC
Frequency60 Hz
Current limiting class3
Over voltage category3
Pollution degree2
Width in number of modular spacings1
Built-in depth70 mm
Degree of protection (IP)IP20
Ambient temperature during operating70 °C
Connectable conductor cross section multi-wired25 mm²
Connectable conductor cross section solid-core35 mm²
Power loss2.62 W
Concurrently switching N-neutralno
Additional equipment possibleyes
Explosion-proofno
Flush-mounted installationyes
The Hager circuit breaker type NBN116 is a 1-pole switching device for protecting electrical circuits in residential and commercial buildings. With a rated current of 16 A and a tripping characteristic B, it provides reliable protection against overload and short circuit. The device is designed for a rated voltage of 400 V and a rated insulation voltage of 500 V, and features a rated switching capacity of 10 kA (Icn) and 15 kA (Icu) at 230 V AC. The protection class IP20 ensures protection against contact with fingers and against solid foreign objects, but not against water or dust. The operating temperature goes up to 70 °C, at which the rated current decreases to 12.04 A. The device is designed for a frequency of 50 to 60 Hz and is suitable for AC networks.

Applications

The circuit breaker is designed for use in distribution enclosures in residential and commercial buildings. It protects electrical wiring and consumers against thermal and mechanical damage caused by overloads or short circuits. Due to its 1-pole design and B characteristic, it is particularly suitable for applications requiring high sensitivity to current overloads, for example in lighting systems or for powering electrical appliances with low inrush current.

Functions and equipment in detail

The switch features a tripping characteristic B, enabling selective disconnection in case of overloads. The rated switching capacities of 10 kA (Icn) and 15 kA (Icu) ensure safe disconnection in case of short-circuit currents. The energy limitation class 3 reduces thermal and mechanical stress in the event of a fault. The connection terminals are designed for single-core conductors up to 35 mm² and multi-core conductors up to 25 mm². Installation is recessed, with an installation depth of 70 mm. The device occupies 1 division unit in the distribution box.

Technology explained simply

The B characteristic means that the switch trips at a current of approximately 1.13 times the rated current (i.e. approximately 18 A) within 1 hour. At 5 times the rated current (80 A), disconnection occurs within 0.1 seconds. The rated switching capacities Icn and Icu describe the maximum short-circuit power that the device can safely disconnect. Icu (15 kA) is the limiting switching capacity, while Icn (10 kA) represents the operational switching capacity. The impulse voltage withstand of 6 kV protects the device against transient voltage surges. The power loss is 2.62 W under rated operation.

Compatibility and accessories

The switch can be combined with various accessories to integrate additional functions. These include auxiliary contacts (MZ201) and signal contacts (MZ202) for status indication or remote control, as well as locking devices (MZN175) for secure access. Cable bridges (K67C, K67H) enable the connection of multiple devices, and phase bars (KDN163A, KDN163B) facilitate installation in distributors. Spacers (LZ060) are used for heat dissipation in densely packed enclosures. The terminals are designed for screw connection, with a nominal torque of 2.80 Nm.

Installation and mounting

Installation is recessed in standard distribution boxes. The installation depth of 70 mm must be taken into account during installation. The connection terminals are designed for screw connection, with the upper terminal offering a 360° screw connection. Mounting is done using the integrated fastening elements. The terminals are suitable for single-core conductors up to 35 mm² and multi-core conductors up to 25 mm². The operating temperature ranges from -25 °C to 70 °C, with the rated current decreasing as the temperature increases.

Advantages in operation

The switch offers high reliability in protecting electrical circuits. The B characteristic enables precise disconnection in case of overloads, thereby extending the service life of connected devices. The high switching capacity of 15 kA (Icu) ensures safety in case of short circuits. The integrated heat dissipation via spacers (optional) reduces thermal stress in the distributor. RoHS compliance ensures the environmental compatibility of the device. The power loss of 2.62 W is low compared to other switches on the market, resulting in more efficient heat dissipation.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/506384
qrcode für Hager NBN116 Circuit Breaker 1P B-16A