General
Release characteristic
B
Number of poles (total)
1
Number of protected poles
1
Rated current
16 A
Rated voltage
400
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
6 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
6 kA
Voltage type
AC
Frequency
60
Current limiting class
3
Over voltage category
3
Pollution degree
2
Width in number of modular spacings
1
Built-in depth
70 mm
Degree of protection (IP)
IP20
Ambient temperature during operating
70
Connectable conductor cross section multi-wired
25
Connectable conductor cross section solid-core
35
Power loss
2.44 W
Concurrently switching N-neutral
Additional equipment possible
Explosion-proof
Flush-mounted installation
The Hager circuit breaker MBS116 is a 1-pole LS switch with B tripping characteristic and a rated current of 16 A. It is designed for use in distribution boards and provides protection against overload and short circuit. With a breaking capacity of 6 kA and a rated voltage of 400 V AC, it is suitable for typical low-voltage installations in residential and commercial areas. The protection class IP20 ensures protection against contact with fingers and against solid foreign objects, but not against water or dust. The operating temperature range is from -25 °C to 70 °C, with the rated current decreasing to 14 A at 70 °C. The switch is intended for mounting in flush-mounted distributors and has a mounting depth of 70 mm.
Applications
The MBS116 is intended for use in electrical distributions indoors, particularly in residential buildings, office buildings, and other facilities where reliable protection against overload and short circuit is required. The B tripping characteristic makes it especially suitable for installations with normal load characteristics, such as lighting, heating, and general consumers. The energy limitation class 3 ensures rapid disconnection in the event of a short circuit, minimizing thermal and mechanical stress on the installation.
Functions and Equipment in Detail
The switch features a QuickConnect connection at the output, enabling quick and secure connection with flexible conductors in cross-sections from 1.5 to 4.0 mm². The input and output terminals are designed for rigid conductors up to 35 mm² and flexible conductors up to 25 mm². The upper terminal is a 360° screw connection, while the lower terminal is of the biconnect type, allowing flexible mounting in modular distributors. The pollution degree class 2 corresponds to an environment with low pollution, as found in normal indoor spaces. The power loss is 2.44 W under rated operation.
Technology Explained Simply
The B tripping characteristic means that the switch disconnects within seconds when the current reaches approximately 3 to 5 times the rated current (i.e., 48 to 80 A). For lower overloads (e.g., 1.13 times), it disconnects after a time delay to tolerate short-term current surges. The breaking capacity of 6 kA is sufficient for most domestic and commercial applications. The rated insulation voltage of 500 V and the impulse voltage withstand of 4 kV ensure safe insulation even under transient voltage surges. The overvoltage category 3 refers to the position in the network and is typical for installations in distribution networks.
Compatibility and Accessories
The MBS116 can be combined with various accessories to integrate additional functions. These include auxiliary contacts (MZ201) and signal contacts (MZ202) for remote monitoring, as well as phase bar systems (e.g., KDN363A, KDN363B, KDN363F) for mounting in modular distributors. Cable bridges (K67C, K67H) enable connection of multiple switches, and end caps (KZN023) protect the phase bar. The locking device MZN175 can be used to secure the switch against unauthorized access. Mounting is done in a 1-module configuration, enabling compact placement in distributors.
Mounting and Installation
Mounting is carried out in flush-mounted distributors using the integrated connection terminals. The upper terminal is a 360° screw connection, and the lower terminal is of the biconnect type, allowing flexible and secure fastening. The rated torque is 2.80 Nm for both terminals. The clearance to the network is 35 mm, ensuring compliance with safety distances. The mounting is designed for modular distributions, with the switch installed in a 1-module size (17.5 mm width).
Advantages in Operation
The MBS116 provides reliable protection with rapid disconnection in the event of a short circuit and controlled response to overload. The QuickConnect technology at the output simplifies installation and maintenance. VDE certification and compliance with EN 60898 and IEC 60947-2 ensure adherence to European safety standards. The energy limitation class 3 minimizes thermal stress on the installation in the event of a fault. The combinability with accessories extends functionality for special applications, such as remote monitoring or protection against unauthorized access.