Further information for Hager ADX482D RCD 4P 32A 30mA
General
Number of poles (total)
4
Number of protected poles
4
Rated voltage
400 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
32 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity Icn acc. EN 61009-1
10 kA
Disconnection characteristic
Undelayed
Surge current capacity
3 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
C
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
40 °C
Width in number of modular spacings
4
Built-in depth
70 mm
Degree of protection (IP)
IP2X
Connectable conductor cross section solid-core
25 mm²
Connectable conductor cross section multi-wired
16 mm²
Power loss
14.6 W
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
The Hager ADX482D is a residual current circuit breaker (RCBO) with 4 poles, designed for protection functions in 400 V three-phase circuits. The device integrates, in a compact 4-pole housing, both the function of a circuit breaker (LS) and a residual current circuit breaker (FI), thereby protecting against overload and short-circuit as well as dangerous residual currents. The design complies with the standard EN/IEC 61009-1, with the residual current protection function designed for type A, enabling detection of pulsating residual currents, such as those occurring in devices with electronic power supplies. The rated residual current is 30 mA, which is standard for protection against electric shock in residential and commercial installations.
Applications
The ADX482D is suitable for use in electrical installations requiring high safety standards for residual current detection, particularly in three-phase systems with 400 V operating voltage. It is intended for indoor use, as the protection rating IP2X provides limited protection against contact with moving parts but does not offer weather protection for outdoor use. The operating temperature is up to 40 °C, with nominal current values decreasing at higher temperatures, as detailed in the technical specification. The overvoltage category 3 and pollution degree 2 indicate use in standard indoor installations without extreme environmental conditions.
Functions and Equipment in Detail
The device features an instantaneous tripping characteristic, meaning it trips immediately upon reaching the residual current or overload current, without delay. The C characteristic is suitable for installations with moderate inrush currents, such as those occurring with motors or heating appliances. The integrated test button in blue enables regular functional testing of the residual current protection. A residual current indicator visually signals the status of the switch. Individual removal from the phase bar system is easily possible, simplifying maintenance and replacement. The locking device ensures the switch can only be removed in the off position, providing additional safety.
Technology Explained Simply
The ADX482D is rated for a nominal current of 32 A, indicating the maximum current it can carry continuously without tripping. The rated short-circuit breaking capacity Icn is 10 kA, describing the maximum current the device can safely interrupt in the event of a short-circuit. The energy limitation class 3 means the device limits the energy fed into the network during a residual current event, reducing damage to downstream equipment. The rated insulation voltage Ui of 500 V and the impulse voltage withstand Uimp of 4 kV ensure sufficient insulation strength against electrical overvoltages. The impulse current withstand of 3 kA describes the maximum current the device can withstand briefly without damage.
Compatibility and Accessories
To extend functionality, various accessories can be retrofitted. These include cable bridges in different cross-sections (e.g. NYAF 6 mm² or 10 mm²) and lengths (100 mm or 250 mm), enabling connections between multiple switches. Spacing elements such as LZ060 are used for heat dissipation during dense mounting. Additionally, auxiliary contacts (MZ201) and signaling contacts (MZ202) are available for signaling the switch status in control or monitoring systems. Direct labeling on the device is possible, facilitating identification of switching functions in the enclosure.
Mounting and Installation
The ADX482D is mounted on standard installation rails (DIN rail). The mounting depth is 70 mm, and the width corresponds to 4 module units (71 mm). The connection cross-sections are designed for single-core conductors up to 25 mm² and multi-core conductors up to 16 mm². Mounting is done via screw terminals, with a nominal torque of 2 Nm for both upper and lower terminals. The device lifespan is 4000 mechanical and 2000 electrical switching operations, ensuring high operational reliability over a long period.
Operational Advantages
The combination of FI and LS functions in a single device reduces space requirements in the enclosure and simplifies installation. Easy individual removal and integrated test and indicator functions facilitate maintenance. The locking device increases safety during mounting and dismounting. The possibility of retrofitting additional components expands application options, especially in complex control systems. RoHS compliance ensures environmental compatibility of the device.