Further information for Hager ADX432D FI-LS 4P 10kA B-32A 30mA A
General
Number of poles (total)
4
Number of protected poles
4
Rated voltage
400 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
32 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity Icn acc. EN 61009-1
10 kA
Disconnection characteristic
Undelayed
Surge current capacity
3 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
B
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
40 °C
Width in number of modular spacings
4
Built-in depth
70 mm
Degree of protection (IP)
IP2X
Connectable conductor cross section solid-core
25 mm²
Connectable conductor cross section multi-wired
16 mm²
Power loss
14.6 W
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
The residual current circuit breaker ADX432D from Hager is a 4-pole circuit breaker that combines overcurrent and residual current protection in a single device. It is designed for use in distribution networks with a rated voltage of 400 V and a rated insulation voltage of 500 V. With a rated current of 32 A and a rated residual current of 30 mA (Type A), it meets the requirements of standard EN/IEC 61009-1. The switch protects against dangerous residual currents, including pulsating direct residual currents, and is therefore suitable for applications where electronic devices with direct current components are operated, such as in IT systems or machines equipped with electronic controls.
Applications
The ADX432D is designed for use in electrical distribution systems, particularly in 400-V networks consisting of three phases and a neutral conductor. It is suitable for installations where high safety against electrical faults is required, such as in residential buildings, commercial or industrial facilities. The tripping characteristic B ensures reliable disconnection in case of overloads and short circuits. The energy limitation class 3 ensures rapid energy limitation in the event of a fault, reducing the thermal stress on the installation.
Functions and equipment in detail
The switch features a switching neutral conductor, meaning that when all phases are disconnected, the neutral conductor is also interrupted. This is important to ensure safe disconnection of the power supply. The tripping characteristic is instantaneous, meaning the switch disconnects immediately upon reaching the tripping threshold. The protection class IP2X protects against contact with solid objects larger than 12.5 mm and is suitable for indoor use. The pollution degree class 2 accounts for slight pollution, as commonly found in normal indoor environments.
Technology explained simply
The switch is designed for a rated short-circuit breaking capacity of 10 kA, meaning it can safely disconnect even under high short-circuit currents. The impulse withstand current is 3 kA, ensuring the mechanical durability of the device under sudden current surges. The rated voltage of 400 V and frequency of 50 Hz correspond to standard network parameters in Europe. The power loss of 14.6 W is expected during operation at rated current and affects the heat generation within the device.
Compatibility and accessories
The ADX432D is designed for installation in standard distribution enclosures with a modular design. The width is 4 module units, and the mounting depth is 70 mm. Suitable accessories include cable bridges in various cross-sections (e.g. NYAF 6 mm² and 10 mm²), spacers for heat dissipation, and auxiliary and signaling contacts. These components allow flexible adaptation to different connection conditions and extend the functionality of the switch, for example by integrating signals for remote monitoring.
Mounting and installation
Mounting is carried out in a modular distribution system, where the switch is connected to the phase busbar via a biconnect lower terminal. The connection cross-sections are up to 16 mm² for flexible conductors and up to 25 mm² for single-core conductors. The recommended torque for the terminals is 2 Nm. The operating temperature range is from -25 °C to 40 °C, with the maximum ambient temperature during operation being 40 °C. The storage and transport temperature can reach up to 70 °C.
Advantages in operation
The switch offers a compact solution for combining overcurrent and residual current protection. The integrated interlock device facilitates safe handling and installation. The possibility to label the switch directly on the device supports clarity in the distribution. The high breaking capacity of 10 kA and energy limitation class 3 increase safety in the event of a fault. The tripping characteristic B ensures reliable response to overloads, which commonly occur in everyday use.