| General |
| Nominal voltage | 0,6/1 kV |
| Test voltage | 4000 V |
| Operation temperature | +90 °C |
| Installation temperature | -5 to +70 °C |
| Temperature after installation | -30 to +70 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Conductor type | bare copper conductor |
| Conductor configuration | RE (round solid) or RM (round stranded) |
| Wire insulation | Cross-linked polyethylene 2XI1 |
| Conductor marking | according to VDE 0293-308 |
| Outer sheath | halogen-free polymer blend |
| Sheath colour | Black |
| Burning behaviour | according to VDE 0472 T. 804, test type C |
| Corrosivity of fire gases | according to VDE 0472 T. 813 |
| Flue gas density | according to VDE 0472 T. 816, test type C |
| Halogen-free | According to VDE 0472 Part 815 |
| Ozone resistance | According to VDE 0472 T. 805 |
| Degree of protection | protective insulation |
| Installation | Not directly in earth or water |
The cable
N2XH-J 4X95,0 SM from Faber Kabel is a halogen-free, protective-insulated power cable designed for applications with high safety requirements. It is used indoors and outdoors, where fire protection and prevention of fire damage to people and property are critical. The cable prevents fire spread under flame exposure and emits only low smoke quantities. It contains no halogen-containing substances, so no corrosive or toxic gases are released in case of fire. Installation is not done directly in earth or water, but in suitable installation systems such as conduits, trunking, or cable ducts.
Applications
This cable is suitable for use in buildings with enhanced fire protection requirements, for example in hospitals, administrative buildings, schools, or industrial facilities. It is used in electrical installations requiring high reliability and fire prevention. Outdoor use is possible, but not for direct earth or water installations. The black-colored outer sheath made of halogen-free polymer blend provides additional protection against external influences.
Functions and Equipment in Detail
The cable consists of bare copper conductors, either round single-strand (RE) or round multi-strand (RM). For a cross-section of 50 mm², the conductors are compacted to ensure optimal current conduction and mechanical stability. The conductor insulation is made of cross-linked polyethylene (2XI1), providing high electrical insulation performance and thermal resistance. Conductor identification follows VDE 0293-308, ensuring clear identification of the conductors. The filler ensures even distribution of the conductors within the cable cross-section.
Technology Explained Simply
The rated voltage is 0.6/1 kV, meaning the cable is designed for electrical installations with an operating voltage up to 1 kV. The test voltage of 4000 V serves quality control and ensures the cable remains stable under increased voltage. The maximum operating temperature is +90 °C, with installation allowed at temperatures from -5 °C to +70 °C. After installation, the cable can be operated at temperatures from -30 °C to +70 °C. The bending radius is 15 times the cable diameter for single-conductor and 12 times for multi-conductor cables, enabling flexible installation.
Compatibility and Accessories
The cable is suitable for use in electrical installations with appropriate installation systems. It can be combined with other cables from the same product range, taking into account the specific requirements of the respective installation. Use in cable ducts, conduits, or trunking is intended. The indication “without function retention” refers to fire behavior properties that do not guarantee special fire protection functions such as maintaining functionality during fire exposure (e.g., according to DIN EN 50219).
Installation and Mounting
Installation is carried out in enclosed systems, such as conduits, cable ducts, or trunking. The cable must not be laid directly in earth or water. Installation must consider the specified temperature ranges. Bending radii must be observed to avoid mechanical damage. Conductors are connected using suitable connection means that meet the requirements of the respective installation.
Advantages in Operation
The cable offers high safety during fire exposure due to low smoke emission and avoidance of toxic gases. The halogen-free composition protects people and materials in case of fire. High electrical insulation performance and thermal resistance ensure reliable operation throughout the entire service life. The black-colored outer sheath provides good protection against external influences and is suitable for outdoor use, provided it is not laid directly in earth or water.