Further information for Faber Kabel N2XSY 1X185 RM/25 12 -
Application:
For laying underground, outdoors, indoors and in cable ducts for power plants, industry and distribution networks.
The cable is easy to lay even on difficult routes due to its good laying properties.
Structure:
Conductor: Bare copper conductor in accordance with VDE 0295,
(RM) round, multi-wire
(>50 mm² are compressed)
extruded inner conductive layer
Core insulation: VPE (cross-linked polyethylene)
extruded outer conductive layer
conductive tape
Shield: Copper wires and cross-conducting spiral
made of copper
foil
Outer sheath: Red PVC
Technical data:
Nominal voltage: 6/10 kV, 12/20 kV and 18/30 kV
Test voltage: 21 kV AC/5 min. at Uo/U=6/10 kV
30 kVAC/5 min. at Uo/U=12/20 kV
45 kV AC/5 min. at Uo/U=18/30 kV
Temperature range: -5 °C - +70 °C (during installation)
-30 °C - +70 °C (after installation)
Operating temperature: +90 °C (max.)
Bending radius: 15 x cable diameter
Flame retardancy: according to VDE 0472 T.
804 test type B (=IEC 332-1).