| General |
| Nominal current | 16 A |
| Rated switching capacity | 10 kA |
| Number of poles | 1 |
| Degree of protection | IP20 |
| Terminal clamp | patented pressure plate |
| Conductor cross section | up to 35 mm² |
| Approvals | DIN VDE 0100-11, IEC/EN 60947-1, DIN VDE 0100-101, IEC/EN 60947-2, UL, CSA 22.2 No. 235 |
The S201M-B16 circuit breaker from the S 200 M series by ESL is a 1-pole circuit protection switch that protects cables and conductors against overload and short circuit. It is designed for use in electrical installations and complies with relevant standards and construction regulations, including DIN VDE 0630-430 and DIN VDE 0630-530. The protection function is achieved through a thermal-magnetic tripping mechanism, which automatically disconnects the circuit in the event of sustained overload or sudden short circuit. The series is designed for use in installation boxes and enclosures and is suitable for applications in building electrical systems as well as industrial installations.
Applications
The S201M-B16 is designed for use in electrical systems with nominal voltages up to 250 V/AC and a nominal current of 16 A. It is typically used in distribution enclosures, flush or surface-mounted installations to protect individual circuits such as lighting, sockets or appliance connections. Compliance with standards DIN VDE 0100-11, IEC/EN 60947-1, DIN VDE 0100-101, IEC/EN 60947-2, as well as UL and CSA 22.2 No. 235, makes it suitable for worldwide use, particularly in countries with strict safety requirements for electrical installations.
Functions and Equipment in Detail
A central feature of the S201M-B16 is the patented connection terminal, which enables secure and easy connection. The terminal is operated via a pressure plate, ensuring a stable and reliable connection to conductors with cross-sections up to 35 mm². The connection opening for the conductors is positioned above the connection opening for the phase bar, simplifying wiring and improving visibility of the connections. The connection terminal is insulated and meets protection class IP20, providing protection against finger contact and against solid foreign objects up to 12.5 mm.
Technology Explained Simply
The circuit breaker operates on the principle of thermal and magnetic tripping. In case of overload, a bimetal strip heats up and disconnects the contact after a certain time. In the event of a short circuit, a high current activates an electromagnet, which immediately disconnects the contact. The nominal current of 16 A means that the switch does not trip at a continuous current of 16 A, but only at higher values. The rated switching capacity of 10 kA describes the maximum short-circuit power that the switch can safely interrupt. These values are crucial for selecting the correct switch depending on the installed wiring and network voltage.
Compatibility and Accessories
The S201M-B16 is part of the S 200 M series, which offers an extensive range of accessories. This includes, for example, additional modules for remote tripping, indicators or additional protection functions that can be added depending on the application. Compatibility with other components of the series enables modular expansion of enclosures and distributions. The mounting width is 18 mm, allowing installation on standard installation rails.
Mounting and Installation
Mounting is carried out in a suitable enclosure or distribution box, taking into account the mounting width of 18 mm. The connection terminal allows direct connection of conductors with cross-sections up to 35 mm², with the insulation of the terminal ensuring protection class IP20. Wiring is done by pressing the pressure plate, which securely fixes the conductor in the terminal. The positioning of the connection openings simplifies work during wiring, especially in complex installations.
Operational Advantages
The S201M-B16 offers high reliability through triple quality inspection before delivery, ensuring that each device meets the requirements for quality and performance. The patented connection terminal reduces installation time and minimizes error sources during wiring. Compliance with international standards and approvals enables use in various markets without additional modifications. Clear marking and easy handling facilitate maintenance and replacement during operation.