Further information for Eltako DSZ15D-3x80A MID (28380015)
Maximum current 3x80A, standby loss only 0.5 watts per path. Modular device for mounting on DIN-EN 60715 TH35 mounting rail. 4 division units = 70mm wide, 58mm deep. Accuracy class B (1%). With S0 interface. The direct measuring three-phase meter measures the active energy based on the currents flowing between the inputs and outputs. The internal consumption of only a maximum of 0.5 watts of active power per path is not measured and not displayed. 1, 2 or 3 external conductors with currents up to 80A can be connected. The starting current is 40mA. The N connection must be present. The 7-segment LC display can also be read twice within two weeks without a power supply. The power consumption is shown in the display with a bar that flashes 100 times per kWh. Can also be used as a 2-tariff meter as standard: Applying 230V to terminals E1/E2 switches to a second tariff. To the right of the display are the MODE and SELECT buttons, which are used to scroll through the menu as per the operating instructions. First, the background lighting switches on. Then the total active energy per tariff, the active energy of the resettable memory RS1 or RS2 and the instantaneous values of power, voltage and current per outer conductor can be displayed. Error message (false): If an outer conductor is missing or the current direction is incorrect, false and the corresponding outer conductor are shown in the display.