| General |
| Operating voltage | 12-230 V UC |
| Control voltage | 12-230 V UC |
| Supply voltage | 12-230 V UC |
| Nominal voltage | 250 V AC |
| Nominal current | 10 A |
| Switching power LED | 200 W |
| Switching capacity incandescent lamp | 2000 W |
| Stand-by loss | 0,02-0,6 W |
| Time range | 0,1-40 s to h |
| Time base | 0.1 s; 0.5 s; 2 s; 5 s; 1 min; 2 min; 5 min; 1 h; 2 h; 4 h |
| Multiplier | 1-10 |
| Functions | 18 |
| Connection | B1-A2 or B2-A2 |
| Mounting | DIN-EN 60715 TH35 |
| Pitch unit | 1 |
| Contact type | Potential free change-over contact |
| Technology | ELTAKO-Duplex technology (DX) |
| Relay type | Bistable |
| Indication | LED |
| Display function | contact position (flashing/open, steady/closed) |
| Function levels | B1-A2 and B2-A2 |
| Functions B1-A2 | RV, AV, TI, TP, IA, EW, AW, ARV, ON, OFF |
| Functions B2-A2 | SRV, ER, EAW, ES, IF, ARV+, ESV, AV+, ON, OFF |
| Load reduction | up to 2 s: 15 %, up to 2 min: 30 %, up to 5 min: 60 % |
| Additional standby loss DX | 0.1 W |
The Eltako MFZ12DX-UC is a modular device for controlling loads via a potential-free changeover contact with a rated voltage of 250 V AC and a rated current of 10 A. It serves as a multifunction timer relay for use in electrical installations, particularly in lighting systems, where a time-controlled switching function is required. The device is designed for mounting on a DIN-EN 60715 TH35 support rail and occupies a mounting space of 18 mm width and 58 mm depth. Control is achieved via a universal control voltage ranging from 12 to 230 V UC, with the supply voltage matching the control voltage.
Applications
This device is suitable for controlling 230 V LED lamps up to a power of 200 W and incandescent lamps up to 2000 W. The maximum load power, however, depends on the set time: from a delay or cycle time of 5 minutes, the full load can be utilized. For shorter times, the maximum load is reduced – to 15 % at 2 seconds, 30 % at 2 minutes, and 60 % at 5 minutes of the rated power. Applications include, for example, stairway lighting, hallway lighting, automatic door openers, or other time-controlled functions in residential and commercial buildings.
Functions and Features in Detail
The MFZ12DX-UC offers 18 different functions, which can be selected depending on the connection of the power supply to terminals B1-A2 or B2-A2. When connected to B1-A2, functions such as release delay (RV), pickup delay (AV), timer with impulse or pause start (TI, TP), impulse-controlled pickup delay (IA), on/off wiper (EW, AW), pickup and release delay (ARV), as well as continuous ON and continuous OFF (ON, OFF) are available. When connected to B2-A2, functions such as inrush switch with release delay (SRV), relay (ER), on/off wiper (EAW), inrush switch (ES), pulse shaper (IF), additive pickup and release delay (ARV+), inrush switch with release delay and off-warning (ESV), additive pickup delay (AV+), as well as continuous ON and continuous OFF (ON, OFF) are available.
Technology Explained Simply
A central feature of the device is the ELTAKO-Duplex technology (DX), which enables switching of potential-free contacts for 230 V AC 50 Hz at the zero crossing. This significantly reduces contact wear. For this, the N conductor must be connected to terminal (N) and the L conductor to 15(L). This results in an additional standby loss of 0.1 W. The device uses a bistable relay, so no coil power loss or heating occurs in the switched-on state. The total standby power loss is 0.02 to 0.6 W, depending on the function level.
Compatibility and Accessories
The device is designed for mounting on a DIN-EN 60715 TH35 support rail and can be integrated into existing installations. Control is via a universal voltage of 12 to 230 V UC. The functions are selectable via the connection configuration at B1-A2 or B2-A2. Time control is achieved via three rotary switches: the top switch (xT) acts as a multiplier from 1 to 10, the middle switch (T) selects the time base (0.1 s, 0.5 s, 2 s, 5 s, 1 min, 2 min, 5 min, 1 h, 2 h, 4 h). The total time is calculated by multiplying the time base by the multiplier, allowing times from 0.1 seconds up to 40 hours to be set. An LED under the large rotary switch indicates the contact position: it blinks when the operating contact 15-18 is open (15-16 closed), and remains lit when 15-18 is closed (15-16 open).
Mounting and Installation
After mounting on the support rail, a short automatic synchronization must be awaited before connecting the controlled load to the network. The connection terminals are clearly labeled, with the power supply connected to B1-A2 or B2-A2 to activate the desired function level. Terminals 15(L) and (N) are used for connecting the load. Time setting is done via the three rotary switches, with the time base and multiplier being selectable independently.
Operational Advantages
The device is characterized by high energy efficiency, as the standby loss is very low (0.02–0.6 W) and no coil losses occur in the switched-on state. The ELTAKO-Duplex technology extends contact life through zero-crossing switching. The wide range of functions allows flexible adaptation to different application scenarios. The clear indication of contact position via the LED simplifies commissioning and maintenance. Mounting on the DIN rail enables quick integration into existing installations.