| General |
| Switching power | 10 A |
| Switching voltage | 250 V AC |
| Control voltage | 12..230 V UC |
| Supply voltage | 12..230 V UC |
| Stand-by loss | 0,05-0,5 W |
| Max. LED power | 200 W |
| Maximum incandescent lamp power | 2000 W |
| Time range | 0,1-99 Seconds, minutes, hours |
| Longest time | 99 Hours |
| Number of time settings | 600 |
| Number of functions | 18 |
| Indication | LC-display |
| Storage medium | EEPROM |
| Relay type | Bistable |
| Mounting | DIN-EN 60715 TH35 |
| Technology | ELTAKO-Duplex (DX) |
The Eltako MFZ12DDX-UC is a
multifunction timer relay designed for use in electrical installations, specifically developed for controlling loads via a
potential-free changeover contact. The device is designed as a plug-in unit and is mounted on a DIN-EN 60715 TH35 support rail. With a width of 18 mm (1 module unit) and a depth of 58 mm, it fits into standard installation enclosures. It features a
universal control voltage of 12 to 230 V UC, where the supply voltage matches the control voltage. Thus, the operating voltage is flexibly adaptable to various mains voltages.
Applications
This timer relay is suitable for controlling lighting systems, particularly
230V LED lamps up to 200W and
incandescent lamps up to 2000W. The maximum load power, however, depends on the set delay or cycle time: full load can be used for times of 5 minutes or longer. For shorter times, the maximum load is reduced – to 15% at up to 2 seconds, 30% at up to 2 minutes, and 60% at up to 5 minutes. Applications include automated lighting, door opener controls, or industrial process controls requiring time-based switching operations.
Functions and Features in Detail
The device offers 18 different
functions, including delayed reset (RV), delayed response (AV), additive delayed response (AV+), timer with impulse or pause start (TI, TP), impulse-controlled delayed response (IA), impulse shaper (IF), on/off wipe (EW, AW, EAW). For functions such as TI, TP, IA, EAW, ARV, and ARV+, a second, independent time can be set, with time frames (seconds, minutes, hours) selectable flexibly. The longest adjustable time is 99 hours. Settings are made via two buttons (MODE and SET), with the LCD display showing the selected function, set time, and contact status symbol. Input is intuitive: pressing MODE selects the element to change (function, time frame, time value), while SET changes the value. The input is confirmed with MODE. After 25 seconds of inactivity with a blinking element, the input mode ends automatically, discarding any previous changes.
Technology Explained Simply
A central feature of the MFZ12DDX-UC is the
ELTAKO Duplex Technology (DX). This enables switching even during 230V AC 50Hz operations at the zero-crossing point, drastically reducing contact wear. For this, the N conductor must be connected to terminal (N) and the L conductor to 15(L). This results in an additional standby loss of only 0.1 W. The device uses a
bistable relay, meaning no coil power loss occurs in the on state, thus avoiding unwanted heating. Total standby loss is between 0.05 and 0.5 W. After installation, a short automatic synchronisation must be awaited before connecting the load to the mains.
Compatibility and Accessories
The device is designed for use in electrical installations with 230V AC. Control is via a universal voltage of 12 to 230 V UC. It is compatible with various load types, especially LED and incandescent lamps, with maximum power depending on the set time. The functions are universally applicable and can be combined according to application context. Display is via an LC display showing the function, set time, and contact status. During the timing process, the current time blinks and the remaining time is displayed.
Mounting and Installation
The device is mounted on a DIN-EN 60715 TH35 support rail. Installation takes place in an electrical enclosure or distribution board. Terminals are clearly marked: (N) for neutral conductor, 15(L) for live conductor. Control voltage connection is made to the appropriate terminals. After mounting, a short automatic synchronisation must be awaited before connecting the load. Settings are made via the MODE and SET buttons, with parameters stored in EEPROM.
Operational Advantages
Safety during power failure is ensured by storing settings in EEPROM. Parameters are immediately available again after a power failure. The low standby power loss of 0.05 to 0.5 W ensures energy-efficient operation. ELTAKO Duplex Technology extends contact life through zero-crossing switching. The digital display enables precise monitoring of function and remaining time. Simple operation via two buttons and the ability to store up to 600 different time settings increase the device’s flexibility and adaptability to various application scenarios.