| General |
| Housing | real glass, plastic, metal |
| Housing colour (similar) | RAL 9010 (white), RAL 9005 (black) |
| Degree of protection | IP20 |
| Dimensions (W × H × D) | 55 mm × 55 mm × 35 mm |
| Installation depth | 7 mm |
| Weight total | ≈ 45 g |
| Ambient temperature | 5…+45 °C |
| rF (relative humidity) non-condensing | 0...95 % |
| Storage temperature | 25...+70 °C |
| Over voltage category | III |
| Pollution degree | 2 |
| KNX bus |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 500 |
| Maximum assignments | 500 |
| Communication objects | 46 |
| Nominal voltage | 30 V DV SELV |
| Electricity consumption | ≤ 19 mA |
| Connection KNX plug-in terminal conductor diameter | Ø 0.8 mm s |
| Connection KNX plug-in terminal stripping length | 5 mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors |
| Temperature measurement range | 5…+60 °C |
The room temperature controller Cala 101 T KNX sec from Elsner is a KNX-compatible device for temperature control in buildings. It measures room temperature and displays the current value in white illuminated digits. The device is designed for use in the KNX building bus system and enables decentralized control of heating and cooling systems. It features a PI controller, which can be used for both single- and two-stage heating and cooling processes. The set temperature is adjusted using touch buttons "+" and "-". The device can function as a main controller or a secondary station within the system and seamlessly integrates into existing switch rows thanks to its standard dimensions of 55 mm × 55 mm × 35 mm. It is supplied with a mounting ring for installation in a switch box.
Applications
The room temperature controller is suitable for use in residential and commercial buildings where precise and comfortable temperature control is required. It is designed for indoor environments where ambient temperature ranges from 5 °C to +45 °C and relative humidity is up to 95 % (non-condensing). The device is intended for indoor use only, as the IP20 protection rating does not provide protection against contact or water. Storage temperature ranges from 25 °C to +70 °C.
Functions and Equipment in Detail
The device measures room temperature in the range of 5 °C to +60 °C. It can receive an external temperature value via the KNX bus and combine it with its own measurement to calculate a mixed value, with the proportion being adjustable in percentage terms. The display shows either the actual temperature, the setpoint, or the base setpoint offset. The touch buttons allow adjustment of the set temperature. The PI controller manages heating and cooling processes based on separate setpoints or a base setpoint. Communication takes place over the KNX network in TP1-256 medium, with the device configured in S-Mode. The maximum number of group addresses and assignments is 500 each, and 46 communication objects are available.
Technology Explained Simply
The controller operates with a nominal voltage of 30 V DC SELV, indicating a safe, low-voltage supply. The maximum current consumption is 19 mA. The KNX plug terminal allows connection to conductors with a diameter of Ø 0.8 mm s and a stripping length of 5 mm. After the bus voltage is restored, it takes approximately 5 seconds for the device to resume data reception. The overvoltage category III and pollution degree 2 indicate intended use in normal indoor environments where no special electrical or chemical stresses occur. The housing is made of real glass, plastic, and metal and is available in the colors RAL 9010 (white) and RAL 9005 (black).
Compatibility and Accessories
The device is designed for the KNX building bus system and operates in TP1-256 mode. It is compatible with KNX Secure, enabling encrypted communication in the network and preventing tampering. The device is supplied with a mounting ring, a KNX plug terminal, and an installation manual in multiple languages (German, English, French, Italian, Spanish). Additionally, a user manual is available for download. Installation is carried out in a switch box, where the device is supplemented with a frame matching the switch series used in the building to ensure a uniform appearance.
Mounting and Installation
Mounting is performed in a standard switch box with a mounting depth of 7 mm. The device is inserted into the box using the included mounting ring and then fitted with the frame of the respective switch series. Electrical connection is made via the KNX plug terminal, designed for conductors with a diameter of Ø 0.8 mm s and a stripping length of 5 mm. Installation is carried out according to the included installation manual.
Advantages in Operation
The room temperature controller offers precise temperature control through the integrated PI controller and the ability to integrate external measurements. Encrypted communication via KNX Secure enhances data security. The touch buttons enable intuitive operation, and the display with white illuminated digits ensures good readability. The device is easy to install and seamlessly integrates visually into existing switch rows. The maximum number of group addresses and assignments allows flexible integration into larger KNX systems.