| General |
| Housing | Plastic |
| Colours (similar) | RAL 9003 / RAL 9002 (white), RAL 9005 (black) |
| Dimensions (Ø × H) | 105 mm × 32 mm |
| Degree of protection | IP30 |
| Weight total | ≈ 55 g |
| Ambient temperature | TH-L-Pr : -5…+45°C, AQS/TH-D L-Pr: 0…+45°C |
| rH (relative humidity), non-condensing | TH-L-Pr : 5...95%, AQS/TH-D L-Pr: 5...85% |
| Storage temperature | TH-L-Pr : -20...+70°C, AQS/TH-D L-Pr: -25...+70°C |
| Over voltage category | III |
| Pollution degree | 2 |
| KNX bus |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 2000 |
| Maximum assignments | 2000 |
| Communication objects | TH-L-Pr : 377, AQS/TH-D L-Pr: 449 |
| Nominal voltage | 30V DC SELV |
| Electricity consumption | ≤ 20mA |
| Connection KNX plug-in terminal conductor diameter | Ø 0.8mm s |
| Connection KNX plug-in terminal stripping length | 5mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors |
| Detection method presence passive infrared technique | PIR |
| Presence detection angle | ≈ 94° × 82° |
| Presence detection range | ≈ 5 m |
| Brightness measurement range | 0 Lux … 2000 Lux |
| CO2 measurement range | 400...5000 ppm |
| Temperature measurement range | 5…+60 °C |
| Humidity measurement range (rH) | 0...100 % |
| Pressure measurement range | 300 mbar … 1100 mbar |
The Elsner Sewi KNX AQS/TH-D L-Pr is a multifunctional ceiling sensor for the KNX bus system, designed for the detection of ambient parameters in indoor environments. The device combines the measurement of presence, brightness, CO2 concentration, temperature, relative humidity, and air pressure in a compact plastic housing. It is used for intelligent control of lighting, ventilation, and air conditioning in office and administrative rooms, where automated, comfortable room climate control is required. The sensors enable precise detection of room conditions and support compliance with standards such as DIN 1946 for comfort. The device is available in the colour deep black RAL 9005 and features a protection rating of IP30, making it suitable for indoor use.
Applications
The sensor is intended for use in office buildings, administrative buildings, schools, and other indoor spaces where automated room climate control and energy savings through intelligent control are required. Detection of presence enables demand-based lighting and ventilation, thereby reducing energy consumption. Measurement of CO2, temperature, and humidity supports monitoring of indoor air quality and compliance with comfort criteria. Air pressure measurement can be used to calculate the dew point, which is relevant for preventing condensation.
Functions and Equipment in Detail
The sensor detects the presence of people using passive infrared (PIR) technology with a detection angle of approximately 94° × 82° and a range of approximately 5 metres. Brightness measurement is performed in the range of 0 to 2000 lux, with lighting being switched off at a user-defined brightness level. CO2 concentration is measured in the range of 400 to 5000 ppm, temperature from 5 to +60 °C, relative humidity from 0 to 100 %, and air pressure from 300 to 1100 mbar. The measured values can be combined into mixed values, with the proportion of internal and external values being adjustable in percentage terms. The sensor can receive external values via the KNX bus and combine them with its own measurements to form overall values.
Technology Explained Simply
The sensor operates in the TP1-256 bus medium and supports the S-Mode configuration mode. Communication takes place at a nominal voltage of 30 V DC SELV, with a maximum current consumption of 20 mA. The connection terminal for the KNX bus is designed for conductors with a diameter of 0.8 mm and a stripping length of 5 mm. The maximum number of group addresses and assignments is 2000 each. The communication objects include 449 entries for the AQS/TH-D L-Pr type. After a bus voltage recovery, it takes approximately 5 seconds before data can be received. Integrated functions include PI controllers for heating, cooling, and ventilation, with ventilation being controlled based on humidity or CO2 concentration. Heating/cooling is controlled based on temperature. Additionally, 8 AND and 8 OR logic gates with 4 inputs each are integrated, which can link switching events and communication objects. 8 multifunction modules enable calculations, condition checks, or data point type conversions. 4 setpoint comparators can calculate minimum, maximum, or average values from 5 inputs. Summer compensation adjusts the set temperature according to the outdoor temperature.
Compatibility and Accessories
The sensor is designed for the KNX bus system and can communicate with other KNX devices. The integrated logic and control functions enable flexible linking with other system components. The devices are available in the colours RAL 9003 / RAL 9002 (white) and RAL 9005 (black). The delivery includes the sensor device, a datasheet with installation instructions in multiple languages (German, English, French, Italian, Spanish), a manual, and a product file for download.
Mounting and Installation
The device is designed for wall or ceiling mounting. The plastic housing has a diameter of 105 mm and a height of 32 mm. Mounting is carried out according to the installation instructions included in the delivery. The ambient temperature for the AQS/TH-D L-Pr is 0 to +45 °C, with relative humidity (non-condensing) of 5 to 85 %. The storage temperature ranges from -25 °C to +70 °C. The overvoltage category is III, and the pollution degree is 2.
Operational Advantages
The sensor enables intelligent, automated control of lighting, ventilation, and air conditioning, thereby reducing energy consumption and optimising indoor air quality. The integrated logic and control functions allow flexible adaptation to different requirements. The mixed value calculation enables the linking of internal and external sensor data, supporting precise room climate control. The bus-based warning when the comfort zone according to DIN 1946 is left supports room climate monitoring. The integrated PI controllers and logic gates reduce the need for additional control devices and simplify the system architecture.