| General |
| Housing | Plastic |
| Colours (similar) | RAL 9003 / RAL 9002 (white), RAL 9005 (black) |
| Dimensions (Ø × H) | 105mm × 32mm |
| Degree of protection | IP30 |
| Weight total | ≈ 50 g |
| Ambient temperature | 0…+45°C |
| Ambient air humidity (rH) (non-condensing) | 5...85% |
| Storage temperature | 25...+70°C |
| Over voltage category | III |
| Pollution degree | 2 |
| KNX bus |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 2000 |
| Maximum assignments | 2000 |
| Communication objects | 363 |
| Nominal voltage | 30V DC SELV |
| Electricity consumption | ≤ 20mA |
| Connection KNX plug-in terminal conductor diameter | 0.6…0.8mm s |
| Connection KNX plug-in terminal stripping length | 5mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors |
| CO2 measurement range | 400...5000 ppm |
| Temperature measurement range | 5…+60 °C |
| Humidity measurement range (rH) | 0...100 % |
| Pressure measurement range | 300 mbar … 1100 mbar |
The Elsner Sewi KNX AQS/TH-D, type 70697, is a
KNX sensor for the acquisition of room climate data, specifically designed for integration into building management systems. The device measures
CO2 concentration,
temperature,
relative humidity, and
air pressure, and processes this data for the control of ventilation and climate systems. It is intended for wall or ceiling mounting and is suitable for use in indoor environments where continuous monitoring of indoor air quality is required. The housing is made of
plastic and is available in the colour
deep black RAL 9005; additional colour variants are RAL 9003 / RAL 9002 (white). Dimensions are Ø 105 mm × 32 mm, and the total weight is approximately 50 g. The protection rating IP30 protects against contact with foreign objects larger than 2.5 mm and against splashing water, but not against direct water jets or precipitation – thus the device is intended for indoor use only.
Applications include office buildings, schools, hospitals, and other spaces where controlled indoor air quality is critical. The sensor monitors comfort according to DIN 1946 by detecting whether the measured values for temperature and humidity lie within the defined comfort range. In case of deviations, it can issue an alarm via the KNX bus. The measured values can be used to control switching outputs, for example, to automatically activate ventilation systems when CO2 limits are exceeded.
Functions and equipment in detail include measuring CO2 concentration in the range of 400 to 5000 ppm, temperature from 5 to +60 °C, relative humidity from 0 to 100 % rH, and air pressure from 300 to 1100 mbar. The sensor calculates the dew point and enables mixed value formation from internal and external measurements, with the proportion being adjustable in percentage terms. The limit values for individual parameters can be set via parameters or communication objects. Integrated
PI controllers enable control of heating, cooling, and ventilation – for example, ventilation based on humidity or CO2 concentration, or heating/cooling based on temperature. Summer compensation adjusts the set temperature according to outdoor temperature to ensure efficient climate control.
Technology explained simply is based on the
KNX bus system with medium TP1-256. Communication takes place in S-Mode, allowing configuration via the KNX software ETS. The device has 363 communication objects, up to 2000 group addresses, and 2000 assignments, enabling flexible integration into existing KNX systems. The nominal voltage is 30 V DC SELV, and the current consumption is ≤ 20 mA. The connection terminal for the KNX bus is designed for conductor diameters of 0.6 to 0.8 mm, with a stripping length of 5 mm. After the bus voltage is restored, it takes approximately 5 seconds before data can be received. The ambient temperature is 0 to +45 °C, and the humidity (non-condensing) is 5 to 85 % rH. The storage temperature ranges from -25 to +70 °C. The overvoltage category III and pollution degree 2 meet the requirements for installations in indoor environments with normal pollution.
Compatibility and accessories include integration into KNX systems. Configuration is performed via the ETS software. The device is equipped with multifunction modules that can modify input data through calculations, condition checks, or data point type conversions. Additionally, 8 AND and 8 OR logic gates are integrated, each supporting 4 inputs. Outputs can be configured as 1 bit or 2 x 8 bits. 4 control value comparators enable output of minimum, maximum, or average values from up to 5 received values. The device is designed for indoor use and requires no additional components for basic functionality.
Mounting and installation is carried out on walls or ceilings. Mounting is done via the integrated housing, which ensures secure fastening. The connection terminal for the KNX bus is directly on the device. Configuration is performed via the ETS software, where settings for sensors, controllers, logic gates, and multifunction modules are made. Installation requires no special tools; the connection terminal is designed for standard conductors.
Operational advantages lie in comprehensive data processing and linking. Integrated functions such as mixed value formation, logic gates, PI controllers, and control value comparators enable flexible and intelligent control of room climate and ventilation systems. The adjustability of limit values and the ability to integrate external measurements increase adaptability to different requirements. The use of KNX technology ensures open and standardised communication within the building management system. The low power consumption and compact design reduce installation effort and operating costs.