| General |
| Degree of protection | IP20 |
| Actuation voltage | 24 V DC |
| Type of current | Direct current |
| Contact arrangement | 4 S |
| Rated operational current (Ith = Ie, 1 pole open at 50 °C) | 10 A |
| Rated operational current AC-15 (220–240 V) | 6 A |
| Rated operating current AC-15 (380–415 V) | 3 A |
| Connection system | Spring clamp terminals |
| Coil power | 2,6 W |
| Contact numbers | according to EN 50011 |
| Coil terminal designation | in accordance with EN 50005 |
| Compliance with standards | IEC/EN 60947, EN 60947-5-1, VDE 0660, UL, CSA |
This product is an auxiliary contactor of the DILER Mini-contactor series by Eaton, type DILER-40-G-C(24VDC), with manufacturer number 230241. It serves as an auxiliary contactor in industrial control systems and is used for signal transmission, status indication, or controlling auxiliary functions in electrical circuits. The device features forced-guided contacts, ensuring reliable and precise switching performance, and is designed for operation with direct voltage. Connection is made via spring-cage terminals, enabling quick and secure connections.
Applications
The auxiliary contactor is designed for use in industrial control systems, particularly in installations combined with DILER contactors of the .DILE-C series. It is commonly used in automation technology, machine building, and manufacturing plants where transmission of switching states or control of auxiliary functions is required. The protection rating IP20 makes the device suitable for use in enclosed enclosures, where no direct access to moving parts is possible.
Functions and Equipment in Detail
The device features four normally closed contacts (4S), serving as auxiliary contacts. Contact numbering conforms to EN 50011, enabling uniform identification and wiring in complex circuits. Operation is performed with a voltage of 24 V DC, with direct current as the current type. The integrated diode-resistor combination protects the control electronics from inductive voltage spikes when the coil is switched off.
Technology Explained Simply
The rated operational current is 10 A (Ith = Ie) at an ambient temperature of 50 °C for an open pole. For alternating voltage AC-15, the rated operational current is 6 A for voltages of 220 V, 230 V, and 240 V, and 3 A for 380 V, 400 V, and 415 V. These values define the maximum current load capacity of the contacts under respective operating conditions. Spring-cage terminals allow for easy and secure connections without additional tools. The protection rating IP20 protects against finger contact and solid foreign objects, but not against water or dust.
Compatibility and Accessories
The auxiliary contactor is specifically designed for use with DILER contactors of the .DILE-C series. It can be combined with various auxiliary switches, including models such as 13DILE, 40DILE-C, 31DILE, 04DILE, 11DILEM, 22DDILE, 11DILE, 02DILEM, 02DILE, XGKE-GE, 20DILE, 11DILE-C, 22DILEM, 13DILE-C, 22DILE-C, 40DILE, 31DILE-C, 04DILE-C, and 22DILE. These accessories extend the functionality of the contactor, for example by adding additional normally closed or normally open contacts, and allow flexible adaptation to specific requirements.
Mounting and Installation
Mounting is performed in standard enclosures or on mounting plates. The spring-cage terminals allow for quick and secure connection of wires. Coil terminal designation follows EN 50005, ensuring uniform and error-free wiring. Installation requires no special tools, as the terminals are mechanically secured.
Advantages in Operation
The forced-guided contacts ensure reliable switching performance, even with frequent switching operations. The integrated diode-resistor combination protects the control electronics from inductive voltage spikes. The spring-cage terminals enable quick and secure connections, reducing installation time. The protection rating IP20 is sufficient for use in enclosed enclosures, where no direct environmental influences occur.
Compliance with standards includes IEC/EN 60947, EN 60947-5-1, VDE 0660, UL, and CSA, confirming adherence to international safety and quality standards. The coil power is 2.6 W, ensuring efficient operation.