Further information for Moeller 170285 FRCMM-16/4/003-A residual current circuit breaker 4-pole 30 mA Type A
General
Rated current
16 A
Rated short-circuit withstand capacity
10 kA
Rated fault current
0,03 A
Protection type
A
Number of poles
4
Application range
industrial and extended commercial applications
Short-circuit resistance with upstream fuse
The residual current circuit breaker FRCMM-16/4/003-A from Eaton is a 4-pole switching device for use in industrial and extended commercial installations. It ensures electrical safety by disconnecting the power supply upon detection of a fault current, protecting personnel and equipment from dangerous touch or fault current situations. The device is rated for a nominal current of 16 A and features a rated short-circuit withstand capacity of 10 kA, with the nominal short-circuit withstand capacity under upstream fuse protection. The rated residual current is 0.03 A, corresponding to Type A, suitable for detecting pulsating fault currents.
Applications
This circuit breaker is designed for use in industrial environments and extended commercial installations where high safety requirements and operational reliability are necessary. It is particularly suitable for installations with electronic loads that may generate pulsating fault currents, such as lighting systems, IT infrastructures, or machine controls. The 4-pole configuration allows disconnection of all conductors, including the neutral conductor, which is required in certain applications.
Functions and Features in Detail
The switch detects fault currents from 0.03 A and automatically trips to interrupt dangerous current flow. The Type A configuration ensures detection of pulsating fault currents, which can occur with modern electronic devices. The rated short-circuit withstand capacity of 10 kA under upstream fuse protection safeguards the device against thermal and mechanical stresses during short-circuit events. The 4-pole construction enables safe disconnection of all phases and the neutral conductor, which is necessary in certain circuits.
Technical Explanation
The residual current circuit breaker operates on the principle of differential current measurement. It compares the current flowing into the load with the current returning. A difference of at least 0.03 A indicates a fault current, triggering the switch to trip. The Type A configuration allows detection of pulsating currents, which occur in devices with rectifier or switch-mode power supply technology. The rated short-circuit withstand capacity of 10 kA under upstream fuse protection means the device can safely disconnect during a short-circuit up to 10 kA, provided an upstream fuse is installed in the circuit.
Compatibility and Accessories
Various accessories are available for this circuit breaker to extend its functionality. These include the reclosing device Z-FW-LP (230 VAC), the remote test module Z-FW/003 (0.03 A), the remote control module Z-FW-MO (ON/OFF/TEST), and the reclosing device set Z-FW-LP/MO. Additionally, the auxiliary switch Z-HK (1NO1NC) and the trip signal switch Z-NHK (2W) are available. These modules can be used depending on requirements for remote control, monitoring, or automatic re-energization of the switch.
Mounting and Installation
The circuit breaker is designed for panel mounting in standard installation enclosures. Installation is carried out in the usual manner within a suitable enclosure or distribution box. The mounting width corresponds to the standard for panel-mounted devices. Electrical connections are made via the designated terminal clamps, with attention to correct polarity and conductor assignment.
Operational Advantages
The use of the FRCMM-16/4/003-A provides high safety through detection of pulsating fault currents. The 4-pole configuration enables complete disconnection of the power supply, which is required in certain installations. The combination with accessory modules extends functionality, e.g., for remote monitoring or automated re-energization. Its reliability under high short-circuit currents with upstream fuse protection makes it suitable for industrial applications.