Dold 0070056, EAN: 4030641700560

Dold 0070056 MK9163N.12PC/110 ATEX AC50/60Hz230V thermistor motor protection relay

Dold 0070056 MK9163N.12PC/110 ATEX AC50/60Hz230V thermistor motor protection relay

Lieske Part No. 1002259
Mfg Part No 0070056
EAN-Code 4030641700560
Manufacturer Dold
Here only 115,21 EUR
137,10 EUR incl. VAT

Further information for Dold 0070056 MK9163N.12PC/110 ATEX AC50/60Hz230V thermistor motor protection relay

Technical data
Auxiliary voltageAC, AC/DC
ClassificationThermistor-Motorschutz
Enclosure designSwitch cabinet
Measuring range max.> 3.8 kΩ
Output contacts2 C/O contacts
Width22,5 mm
TypeMK 9163N ATEX
Variant
Contact equipping2 changeover contacts
Nominal voltageAC 230 V
Terminal typepluggable terminal blocks with cage clamp terminals
Approvals and MarkingsATEX
VariantWith short circuit detection. With RESET and test function via built in button and X1/X2
The Dold thermistor motor protection relay MK9163N.12PC/110 ATEX AC50/60HZ230V is an enclosure device for temperature monitoring of electric motors and other thermally stressed components such as bearings, gearboxes, oils or coolants. It serves to prevent thermal overloads that may arise due to high switching frequency, heavy start-up, single-phase operation, impaired cooling, or high ambient temperature. The device monitors the resistance of thermistors and responds to temperature exceedances, wire breaks in the sensor circuit, and short circuits in the sensor circuit. The function is based on the stand-by current principle, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable fault detection.

Applications
This relay is designed for use in industrial plants, particularly in environments where high reliability of temperature monitoring is required. It is suitable for protecting electric motors in pumps, fans, conveyor systems, and other machinery operating under variable operating conditions. The ATEX certification allows use in explosive atmospheres, with specific categories and zones to be considered according to standards EN 60079-14 and EN 61508. The device is installed in enclosures, with a width of 22.5 mm enabling compact mounting in standard control panels.

Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary functions or alarms. Indication is provided via LEDs, displaying the status of auxiliary voltage and contact position. The MK9163N.12PC/110 ATEX variant includes short-circuit detection and offers reset and test functions, which can be activated via a button on the device as well as through terminals X1/X2. This enables quick fault localization and restoration of operational status. The connection terminals are designed as removable terminal blocks with spring pressure clamps, allowing flexible and rapid installation. Wire connections can be made with 2 x 1.5 mm² stranded wire with ferrule and plastic sleeve or 2 x 2.5 mm² solid wire according to DIN 46 228-1/-2/-3/-4.

Technology Explained Simply
The operation is based on measuring the resistance of thermistors installed in the motor or the component to be monitored. The device’s measurement range is up to 3.8 kΩ. If the resistance deviates from the predefined limits, for example due to temperature rise, wire break, or short circuit, a fault is detected. The relay responds by switching the output contacts accordingly, triggering an alarm or shutting down the motor. The auxiliary voltage can be used in AC or AC/DC operation, with the nominal voltage being AC 230 V. The classification as a thermistor motor protection relay refers to its specific application for monitoring motors via thermistors.

Compatibility and Accessories
The device is designed for use with 3 or 6 thermistors, with the exact number and arrangement varying depending on the application. The connection terminals allow flexible wiring, with spring pressure clamps ensuring a secure and reliable connection. The ATEX certification permits use in explosive atmospheres, with specific requirements to be met according to standards EN 60079-14 and EN 61508. The standards EN 60947-5-1, EN 60947-8, EN 13849, and EN 50495 apply to the functionality and safety of the device. The use of additional accessories such as plug-in terminal blocks is optional and enables quick device replacement.

Mounting and Installation
Mounting is carried out in an enclosure, with a width of 22.5 mm allowing standard installation in DIN control panels. The connection terminals are designed for use with stranded or solid conductors according to DIN 46 228. The thermistors are wired to the device’s input, with the number of thermistors (3 or 6) varying according to configuration. Terminals X1/X2 serve the remote reset and test functions, simplifying maintenance and diagnostics. The LED indicators allow visual inspection of the operational status.

Advantages in Operation
The reliability of temperature monitoring is ensured by detecting temperature exceedances, wire breaks, and short circuits. Quick fault localization via reset and test functions reduces downtime. The ATEX certification expands the application range to hazardous environments. The combination of spring pressure clamps and removable terminal blocks enables flexible and rapid installation. The width of 22.5 mm optimizes space requirements in enclosures. The use of thermistors as sensors provides precise and reliable temperature measurement, which is crucial for protecting motors and other components.