pluggable terminal blocks with cage clamp terminals
Approvals and Markings
UL-listed C/US, TÜV, UKCA, CCC
The Dold emergency stop module type LG5925.48PC/61 AC110-115V is a safety-relevant switching component for use in industrial plants, particularly for protecting machines and combustion systems. It serves for hazard disconnection and monitoring of sliding safety grilles, as well as for protective door monitoring. The device is designed for operation with a nominal voltage of AC 110–115 V at 50/60 Hz and has a width of 22.5 mm, making it suitable for standard DIN control panels. The contact configuration includes 3 normally closed contacts and 1 normally open contact, with up to 4 normally closed contacts usable as output contacts. The connection technology uses removable spring clamps, with removable screw clamps and screw clamps also specified as options. The terminals are rated for conductor cross-sections up to 2.5 mm² solid (DIN 46228-1/-2/-3/-4) or 1.5 mm² stranded wire with ferrule and plastic sleeve.
Applications
This module is used in plants requiring safe disconnection in hazardous situations. This includes emergency stop circuits for machines, monitoring of sliding safety grilles, and disconnection of the entire fuel supply in combustion systems in accordance with EN 50156-1. It is also intended for continuous operation in combustion systems according to EN 50156-1. The protective door monitoring function enables monitoring of protective covers to ensure they are closed before the machine is started.
Functions and Equipment in Detail
The device supports single- or dual-channel wiring, allowing flexible use in different safety configurations. It features cross-connection detection, preventing incorrect control due to accidental connections between channels. Activation is via a single button or an automatic start function, which can be set using switch S2. Operating states are visually indicated by LEDs for channel 1, channel 2, and supply voltage. The connection terminals are removable, enabling module replacement without dismantling the entire circuit.
Technology Explained Simply
The safety functions of the module are based on standards EN ISO 13849-1 and IEC/EN 62061. It meets category 4 and performance level (PL) e according to EN ISO 13849-1, indicating high safety performance in critical applications. Additionally, it complies with the safety integrity level (SIL) requirement limit (SIL CL) 3 according to IEC/EN 62061, as well as Safety Integrity Level (SIL) 3 according to IEC/EN 61508 and IEC/EN 61511. These certifications guarantee that the device can be used in safety-critical plants where failure could lead to hazards for personnel or machinery. The maximum thermal current is 8 A, defining the contact load capacity.
Compatibility and Accessories
The module is designed for use in systems requiring safe control. It can be combined with other components that also meet the requirements of the mentioned standards. The removable terminal blocks allow for quick installation and maintenance. Certifications UL-listed C/US, TÜV, UKCA, and CCC confirm compliance with international safety standards.
Mounting and Installation
Mounting is performed in standard DIN control panels with a width of 22.5 mm. The connection terminals are designed for various conductor cross-sections, with the use of ferrules and plastic sleeves recommended for stranded wires. The LED indicators facilitate commissioning and troubleshooting. The single button and switches S1 and S2 allow flexible configuration of operating modes.
Advantages in Operation
The module provides high safety performance through integrated cross-connection detection and certifications according to international standards. The removable terminal blocks reduce installation and maintenance times. The LED indicators enable quick diagnosis of operating states. Use in combustion systems and emergency stop circuits makes it a reliable component in safety-critical plants. Compliance with UL, TÜV, UKCA, and CCC ensures suitability for various markets.