Further information for Dold 0069878 RN5893.12/010/61 ACDC24-60V 1K-500K insulation monitor
Technical data
Approvals
UL-Recognized
Bus interface
Modbus RTU
Classification
For DC charging stations
Enclosure design
Distribution board
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 230 V, AC 0 - 690 (Coupling device) V, DC 0 - 230 V, DC 0 - 1000 (Coupling device) V
Response value
1 - 500 kΩ
Response value type
Adjustable
Width
52,5 mm
Type
RN 5893
Earth fault indicator
Variant
Alarm value
1 - 500 kOhm
Auxiliary voltage
AC/DC 24 - 60 V
Contact equipping
2 x 1 changeover contact
Prewarning value
1 - 500 kOhm
Approvals and Markings
UL-rec. C/US
Variant
Für Netzableitkapazitäten bis 30 µF
The insulation monitor RN5893.12/010/61 from Dold is a device for monitoring insulation quality in ungrounded IT systems, particularly in DC charging stations for electric vehicles. The device belongs to the VARIMETER IMD family and is designed for use in AC, DC, and mixed AC/DC networks. It complies with the requirements of standard IEC/EN 61557-8 and is suitable for nominal voltages up to AC 230 V or DC 230 V. With an external pre-stage device RP 5898, higher voltages up to AC 690 V and DC 1000 V can also be monitored. The auxiliary voltage is AC/DC 24–60 V, and the device is designed for network capacitances up to 30 µF.
Applications
The insulation monitor is primarily intended for DC charging stations in accordance with IEC/EN 61851-23:2014/AC:2016-06, but also provides protection in other applications such as UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery vehicles, as well as mobile power generators. Monitoring is also performed when the network is de-energized, ensuring continuous safety functionality.
Functions and Equipment in Detail
The device features two independently adjustable trip thresholds in the range of 1 kΩ to 500 kΩ, allowing a pre-alarm level and an alarm level to be defined. Adjustment is made via two rotary switches on the front of the device. A multi-colored illuminated display shows the current insulation resistance, device status, and enables parameterization. The earth fault indication is integrated. The response time for the RN5893/010 variant is less than 10 seconds.
Technology Explained Simply
Insulation monitoring is performed using the VARIMETER IMD technology principle, detecting both symmetrical and asymmetrical insulation faults. Selective earth fault detection for L+ and L– enables rapid fault localization. Wire break monitoring for L(+) and L(–) is switchable off, while wire break monitoring for the protective conductor PE1/PE2 is not switchable off. The measurement is optimized even during network voltage fluctuations, as the network voltage is evaluated.
Compatibility and Accessories
The device is equipped with a galvanically isolated Modbus RTU interface, via which all measured values, device statuses, and parameters can be read, set, and parameterized. The device functions can also be controlled via Modbus. Combining it with the external pre-stage device RP 5898 extends the application range to higher voltages.
Mounting and Installation
The insulation monitor is designed as an installation distributor with a width of 52.5 mm. Mounting is done in standard distributor enclosures. The tamper-proof transparent cover protects the device against unauthorized manipulation. An external control input allows connection of a combined test/reset button with an additional stop function for the measurement function.
Operational Advantages
The device provides preventive fire and system protection through early detection of insulation faults. The galvanically isolated changeover contacts (2 x 1 changeover contact) allow assignment of different alarm functions, such as pre-alarm, alarm, or device error. Alarm storage is selectable, and a manual device self-test is available. The operating or standby current principle for the alarm relays is adjustable, facilitating integration into existing safety concepts.