Further information for Dold 0069877 RN5893.12/61 insulation monitor 1K-500K
Technical data
Approvals
UL-Recognized
Bus interface
Modbus RTU
Classification
For DC charging stations
Enclosure design
Distribution board
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 230 V, AC 0 - 690 (Coupling device) V, DC 0 - 230 V, DC 0 - 1000 (Coupling device) V
Response value
1 - 500 kΩ
Response value type
Adjustable
Width
52,5 mm
Type
RN 5893
Earth fault indicator
Variant
Alarm value
1 - 500 kOhm
Auxiliary voltage
AC/DC 100 - 240 V
Contact equipping
2 x 1 changeover contact
Prewarning value
1 - 500 kOhm
Approvals and Markings
UL-rec. C/US
Variant
Für Netzableitkapazitäten bis 5 µF
The isolation monitor RN5893.12/61 from Dold is a device for monitoring insulation quality in ungrounded IT systems. It is specifically designed for use in DC charging stations for electric vehicles and meets the requirements of standard IEC/EN 61851-23:2014/AC:2016-06. The device enables continuous monitoring of AC, DC, and mixed AC/DC networks and is directly applicable for nominal voltages up to AC 230 V and DC 230 V. When used with an external pre-stage device RP 5898, higher voltages up to AC 690 V and DC 1000 V can also be monitored. Insulation monitoring is performed according to IEC/EN 61557-8, detecting both symmetrical and asymmetrical insulation faults. Selective earth fault detection on L+ and L- enables rapid fault localization.
Applications
The RN5893 is universally applicable in various application areas, including DC charging stations for electric vehicles, UPS systems, networks with frequency converters, battery networks, networks with DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. Monitoring is also performed when the network is de-energized, ensuring continuous safety. The device is designed for network leakage capacitances up to 5 µF.
Functions and Equipment in Detail
The device features two independently adjustable trip thresholds, which can be used for pre-alarm and alarm functions. The adjustment range for both values is between 1 kΩ and 500 kΩ. Adjustment is performed via two rotary switches on the front of the device, enabling user-friendly parameterization. A multicolored illuminated display shows the current insulation resistance, device status, and additional parameters. The earth fault indication is integrated. The measurement circuit monitoring L(+)/L(-) detects wire breaks and is switchable off, while the protective conductor connection monitoring PE1/PE2 also detects wire breaks but is not switchable off.
Technology Explained Simply
The insulation resistance measurement is optimized to function reliably even during network voltage fluctuations. This is achieved by evaluating the network voltage. The device's response time is ≤ 1 s, enabling rapid reaction to insulation faults. The alarm relays are galvanically isolated and configurable; they can be set for various functions such as insulation fault pre-alarm, insulation fault alarm, insulation fault alarm on DC+/DC-, or device fault. A manual device self-test is available, and an automatic self-test can be activated. Alarm storage is selectable, and an external control input enables the use of a combined test/reset button with an additional stop function for the measurement function.
Compatibility and Accessories
The device is equipped with a galvanically isolated Modbus RTU interface, via which all measurement values, device statuses, and parameters can be read, set, and parameterized. All functions of the device are accessible via the Modbus interface. The auxiliary voltage is AC/DC 100–240 V, enabling flexible integration into existing power supplies. The width is 52.5 mm, allowing installation in standard installation distributors. UL-Recognized (C/US) certification is provided.
Mounting and Installation
The isolation monitor RN5893 is designed as an installation distributor and can be mounted in standard switchboards. The tamper-proof transparent cover protects the device against unauthorized manipulation. Mounting is tool-free, with connection points for auxiliary voltage and measurement circuits clearly marked. Parameterization is performed either via the front rotary switches or via the Modbus interface.
Operational Advantages
Operation of the RN5893 provides preventive fire and system protection through early detection of insulation faults. The fast response time and selective fault localization reduce downtime. The Modbus interface enables integration into higher-level control and monitoring systems. Simple operation and clear display ensure high user-friendliness. Galvanic isolation of the contacts increases the safety and reliability of the system.