Dold 0069876, EAN: 4030641698768

Dold 0069876 RN5893.12/61 AC/DC24-60V 1K-500K insulation monitor

Dold 0069876 RN5893.12/61 AC/DC24-60V 1K-500K insulation monitor

Lieske Part No. 1001708
Mfg Part No 0069876
EAN-Code 4030641698768
Manufacturer Dold
Here only 692,36 EUR
823,91 EUR incl. VAT

Further information for Dold 0069876 RN5893.12/61 AC/DC24-60V 1K-500K insulation monitor

Technical data
ApprovalsUL-Recognized
Bus interfaceModbus RTU
ClassificationFor DC charging stations
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 230 V, AC 0 - 690 (Coupling device) V, DC 0 - 230 V, DC 0 - 1000 (Coupling device) V
Response value1 - 500 kΩ
Response value typeAdjustable
Width52,5 mm
TypeRN 5893
Earth fault indicatorYes
Variant
Alarm value1 - 500 kOhm
Auxiliary voltageAC/DC 24 - 60 V
Contact equipping2 x 1 changeover contact
Prewarning value1 - 500 kOhm
Approvals and MarkingsUL-rec. C/US
VariantFür Netzableitkapazitäten bis 5 µF
The isolation monitor RN5893.12/61 from Dold is a device for monitoring insulation quality in ungrounded IT systems. It is specifically designed for use in DC charging stations for electric vehicles operated in accordance with IEC/EN 61851-23:2014/AC:2016-06. The device enables continuous monitoring of AC, DC, and mixed AC/DC networks and is directly applicable for nominal voltages up to AC 230 V and DC 230 V. When used with an external pre-stage device RP 5898, higher voltages up to AC 690 V and DC 1000 V can also be monitored. Insulation monitoring is carried out in accordance with the standard IEC/EN 61557-8, ensuring the reliability and safety of the installation.

Applications

The RN5893.12/61 is universally applicable in various application areas, including ungrounded AC and DC networks, UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. The primary application, however, lies in the monitoring of DC charging stations for electric vehicles, where high safety and rapid fault detection are required. The detection of symmetrical and asymmetrical insulation faults enables precise fault localization, thereby increasing the availability of the installation.

Functions and Equipment in Detail

The device features two independently adjustable trip thresholds in the range of 1 kΩ to 500 kΩ, which can be used for pre-alarm and alarm functions. Adjustment is performed via two rotary switches on the front of the device, ensuring user-friendly parameterization. Additionally, parameterization can be carried out via a Modbus RTU interface, enabling integration with higher-level control and monitoring systems. Display is provided via a multi-colored illuminated display, showing the current insulation resistance, device status, and other parameters. A manual device self-test is available, and an automatic self-test can also be activated. Alarm storage is optional, allowing previous alarms to be reviewed even after a reset.

Technology Explained Simply

Insulation monitoring is performed by measuring the insulation resistance between conductors L+ and L- and the protective earth conductor PE. The device detects insulation faults even in de-energized networks, enabling continuous monitoring even during standby operation. Wire break monitoring for L(+) and L(-) is switchable off, while wire break monitoring for protective earth conductors PE1/PE2 is not switchable off. The response time is ≤ 1 second, enabling rapid reaction to insulation faults. The network leakage capacitance is limited to a maximum of 5 µF for this type, enabling application in systems with low capacitance.

Compatibility and Accessories

The device is designed for use with an external pre-stage device RP 5898, which enables monitoring of higher voltages up to AC 690 V and DC 1000 V. The Modbus RTU interface allows integration into existing building or plant control systems. The auxiliary voltage can operate in the range of AC/DC 24–60 V, enabling flexible connection to various power sources. The width is 52.5 mm, allowing installation in standard installation distributors.

Mounting and Installation

The isolation monitor RN5893.12/61 is mounted in an installation distributor. Mounting is performed in a standard switch cabinet, taking into account the width of 52.5 mm. The connection terminals are designed for connection to network conductors L+, L-, and PE, as well as for auxiliary voltage. The Modbus interface enables a serial connection to a higher-level system. The tamper-proof transparent cover protects the device from unauthorized manipulation and ensures secure operation.

Advantages in Operation

Operation of the RN5893.12/61 provides preventive fire and system protection through early detection of insulation faults. Selective earth fault detection according to L+ and L- enables rapid fault localization. The galvanically isolated changeover contacts (2 x 1 changeover contact) can be parameterized for various alarm functions such as pre-alarm, alarm, or device failure. The Modbus RTU interface enables centralized monitoring and remote control, making maintenance and diagnostics more efficient. The adjustability of trip values and flexible adaptation to different network types increases the operational flexibility of the device.
This is an offer of: