| Technical data |
| 1- / 3-phase | 3 |
| Auxiliary voltage | Without |
| Bus interface | Modbus RTU |
| Enclosure design | Distribution board |
| Measuring range max. | 230 V |
| Standard measuring range | 3/N AC 80 - 230 V |
| Width | 35 mm |
| Type | RL 9405 |
| Variant |
| Nominal voltage | 3/N AC 80 - 230 V / 140 - 400 V 50 Hz |
| Variant | Sekundärnennspannung der Stromwandler 333 mV |
The RL9405/333 energy meter from Dold is a 3-phase measuring device for low-voltage networks with neutral conductor, designed for continuous monitoring of electrical parameters and energy consumption. It belongs to the VARIMETER PRO series and is specifically designed for use in enclosures and installation small distributors. The device measures voltages and currents in real time and calculates values such as active power, reactive power, apparent power, power factor, network frequency, as well as active, reactive, and apparent energy. The measured values are read out via a galvanically isolated Modbus RTU interface, ensuring secure and interference-free communication with higher-level control or monitoring systems. The width is 35 mm, making it particularly suitable for tight space conditions.
Applications
The RL9405/333 energy meter is intended for measurement in 3-phase networks with neutral conductor (IT-, TN- or TT-systems). It is suitable for monitoring energy consumption in industrial plants, production environments, building technology, and other applications where accurate recording of electrical parameters is required. Measurement is performed in the range of 3/N AC 80–230 V / 140–400 V at a nominal frequency of 50 Hz. The maximum measurement voltage is 230 V, with the standard measurement range covering 3/N AC 80–230 V. Measurement accuracy is ±0.5 %, ensuring reliable data acquisition.
Functions and Equipment in Detail
The device continuously records the effective and peak values of phase voltage and phase current. Additionally, network frequency, power factor, active power, reactive power, apparent power, active energy, reactive energy, and apparent energy are calculated. The measured values are permanently stored in the device, so that energy consumption data remain available even after power supply interruption. The Modbus RTU interface allows configuration of the Modbus address (1 to 99) and baud rate (9600, 19200, 38400) directly on the device. Current transformer ratios can be set via Modbus, enabling adaptation to market-standard current transformers with 100 mA, 1 A, or 5 A secondary rated current, as well as to the variant with 333 mV secondary rated voltage. The current measurement inputs are not galvanically isolated, so external current transformers are required.
Technology Explained Simply
The energy meter is powered via the voltage measurement inputs of the three phases, eliminating the need for a separate auxiliary supply. Power consumption is approximately 1 VA. Measurement is performed via inputs L1, L2, L3, and N for voltage, and i1, k1, i2, k2, i3, k3 for current measurement. The RS485 interface (terminals A, B, GND) enables communication via Modbus RTU. The galvanic isolation of the interface protects the device and connected systems from interference. Indication is provided by a green LED (ON, when operating voltage is present) and a yellow LED (BUS, during RS485 bus activity).
Compatibility and Accessories
The RL9405/333 energy meter is designed for use with current transformers having a secondary rated voltage of 333 mV. It can be connected to current transformers with 100 mA, 1 A, or 5 A secondary rated current, with the turns ratio adjustable via Modbus. Measurement ranges extend up to 1000 A when using external current transformers. Communication is via Modbus RTU, enabling integration into existing control and monitoring systems.
Mounting and Installation
The device is designed as an installation distributor and can be installed in enclosures or installation small distributors. The width of 35 mm allows for compact mounting. Connections are made via the designated terminals for voltage (L1, L2, L3, N) and current (i1, k1, i2, k2, i3, k3), as well as the RS485 interface (A, B, GND). Mounting is done in the usual manner for DIN rail or perforated sheet metal mounting, with detailed mounting instructions available in the datasheet.
Operational Advantages
The compact design with a width of 35 mm frees up more space in the enclosure. Permanent storage of energy measurement values ensures that consumption data remain available even after a power failure. The galvanically isolated Modbus RTU interface ensures reliable data transmission. The ability to set Modbus parameters directly on the device enables easy configuration. Power supply from the measurement voltage reduces the number of required supply lines. The device is not intended for billing purposes under EU Directive 2004/22/EC (MID) and therefore must not be used for active energy measurements for billing.