Further information for Dold 0069309 still-run monitor UH=DC24V
Technical data
Classification
Sensorless, Stillstandsüberwachung
Enclosure design
Switch cabinet
Measuring range max.
4 V, 400 mV
Output contacts
1 NC contact, 2 NO contacts
Width
22,5 mm
Type
UG 9146
Operate delay
Variant
Auxiliary voltage
DC 24 V
Contact equipping
2 NO contacts, 1 NC contact
Response value
0,2 - 4 V
Terminal type
plug in terminal blocks with cage clamp terminals
Time range
0,2 - 6 s
Approvals and Markings
UL-listed C/US, UKCA
The Dold UG9146.22PC/61 is a sensorless standstill monitor used for monitoring electric motors for standstill. The device measures the induced voltage at two terminals of the stator winding of the decelerating motor. When the induction voltage approaches zero, the device detects motor standstill and activates the output relay. The function is based on the residual magnetization (remanence) of the motor, which generates a voltage during deceleration proportional to the rotational speed. The standstill monitor is suitable for 3- and 1-phase motors and operates independently of rotation direction.
Applications
The UG9146 is used in production plants where speed-dependent switching is required, for example, to activate holding brakes or to signal to higher-level control systems. It is particularly suitable for systems where retrofitting is to be carried out without additional sensors or initiators. Use with frequency converters is also possible, facilitating integration into modern drive technology.
Functions and Equipment in Detail
The device features adjustable parameters: the voltage threshold (pickup value) can be set in the range of 0.2 to 4 V to adapt detection to different motors. The standstill time, i.e., the time the voltage must remain below the threshold before the output is activated, is adjustable between 0.2 and 6 seconds. This adjustability allows precise adaptation to different drive conditions. Additionally, the device detects wire breaks in the measurement circuit L1/L2 and responds by deactivating the output relay—a state that remains stored depending on the setting.
Technology Explained Simply
Measurement is performed via terminals L1/L2, which are connected to the motor winding. The induced voltage is continuously monitored. When it falls below the set threshold, the time delay (standstill time) begins. After this time has elapsed, the output is activated. The output contacts are forced-guided: there are two normally open contacts (for AC 250 V) and one normally closed contact (for DC 24 V). The auxiliary voltage is DC 24 V and is supplied at terminals A1/A2. Operational readiness is indicated by a green LED UH". In case of internal faults, this LED lights red. A yellow-green LED "OUT" indicates the output status: yellow when voltage is above the threshold, green flashing during standstill time, and green continuously when the output is activated. A red LED "ERR flashes in case of faults.
Compatibility and Accessories
The standstill monitor is compatible with 3- and 1-phase electric motors that generate a remanence voltage during coast-down. The device connections consist of plug-in terminal blocks with spring-clamp terminals (type PC). The width is 22.5 mm, enabling installation in standard enclosures. The devices comply with the standard DIN/EN 60255-1. Approvals include UL-listed C/US and UKCA.
Mounting and Installation
Mounting is done in an enclosure. The connections are clearly labeled: L1/L2 for the motor, A1/A2 for auxiliary voltage, 31/32 for the alarm output, 13/14 and 23/24 for the normally open contacts. The spring-clamp terminals allow quick and secure connections without tools. The settings for voltage threshold and standstill time are adjusted via rotary dials on the device. The LED indicators support commissioning and maintenance.
Advantages in Operation
The sensorless operation reduces the number of required components and lowers maintenance effort. The fast response time and adjustability of parameters enable flexible use in various applications. Wire break detection increases safety, as a faulty measurement circuit is detected and appropriately responded to. The forced-guided contacts ensure secure signal transmission.