Dold 0069308, EAN: 4030641693084

Dold 0069308 UG9146.22PC/61 20-400mV 0.2-6s still-run monitor

Dold 0069308 UG9146.22PC/61 20-400mV 0.2-6s still-run monitor

Lieske Part No. 1153147
Mfg Part No 0069308
EAN-Code 4030641693084
Manufacturer Dold
Here only 356,33 EUR
424,03 EUR incl. VAT

Further information for Dold 0069308 UG9146.22PC/61 20-400mV 0.2-6s still-run monitor

Technical data
ClassificationSensorless, Stillstandsüberwachung
Enclosure designSwitch cabinet
Measuring range max.4 V, 400 mV
Output contacts1 NC contact, 2 NO contacts
Width22,5 mm
TypeUG 9146
Operate delayYes
Variant
Auxiliary voltageDC 24 V
Contact equipping2 NO contacts, 1 NC contact
Response value20 - 400 mV
Terminal typeplug in terminal blocks with cage clamp terminals
Time range0,2 - 6 s
Approvals and MarkingsUL-listed C/US, UKCA
The sensorless standstill monitor UG 9146 from Dold is used for monitoring electric motors for standstill without the use of external sensors. The device measures the induced voltage at two terminals of the stator winding of the decelerating motor. When the induction voltage drops to zero, this is interpreted as motor standstill and the output relay switches on. The function is based on the remanent voltage, which is generated during motor deceleration due to residual magnetization. The application is in enclosures and is suitable for monitoring 3- and 1-phase motors, regardless of rotation direction. The device class corresponds to DIN/EN 60255-1, confirming its classification in industrial switching technology.

Standstill monitoring is achieved by measuring the induced voltage. The voltage threshold, below which standstill is detected, is adjustable in the range of 20 to 400 mV. Additionally, the standstill time is adjustable between 0.2 and 6 seconds, allowing adaptation to the specific requirements of the installation. This adjustability enables flexible use with different motors and drive systems. The device connections consist of pluggable terminal blocks with spring-cage terminals, ensuring quick and secure installation. The width is 22.5 mm, enabling compact installation in standard enclosures.

Functions and equipment in detail include forced-guided output contacts: two normally open contacts for AC 250 V and one normally closed contact for DC 24 V. This configuration enables integration into safety and control systems. The auxiliary voltage is DC 24 V, supplied via terminals A1-A2. Operational readiness is indicated by a green LED UH". In case of internal faults, this LED lights red. A yellow-green LED "OUT" indicates operation via EMF, flashes green during standstill time, and remains green when output contacts are released. A red LED "ERR flashes in case of faults. The device also detects wire breaks in the measurement circuit L1/L2 and deactivates the output relay, corresponding to the state of a running motor. This state can be stored.

Technology explained simply is based on measuring the back EMF (EMK) during motor coast-down. The voltage is proportional to rotational speed and is generated by remanence. When the voltage falls below the set threshold, standstill is detected. The response delay ensures that short-term voltage fluctuations are not interpreted as standstill. The devices are suitable for use with frequency converters, enabling application in modern drive systems. The certifications UL-listed C/US and UKCA confirm compliance with relevant safety and quality standards.

Compatibility and accessories include use with 3- and 1-phase electric motors that generate remanent voltage during coast-down. Device connection variants UG 9146 PS (screw terminals) and UG 9146 PC (spring-cage terminals) are available, with the variant described here using spring-cage terminals. The output contacts are designed for use in safety circuits. The devices are designed for use in enclosures and meet the requirements of industrial electrical engineering.

Mounting and installation is carried out in standard enclosures. The pluggable terminal blocks with spring-cage terminals enable quick and secure connections. Terminal designation L1-L2 is for connection to the motor, A1-A2 for auxiliary voltage. Output contacts 13-14 and 23-24 are intended for release circuits, while 31-32 serves as alarm output. Adjustments for voltage threshold and standstill time are made via the designated adjustment options on the device.

Advantages in operation include easy retrofitting without additional sensors, fast response time, and reliability through wire break detection. The adjustability of parameters allows adaptation to different motors and applications. The LED indicators provide visual feedback on operating status, facilitating maintenance and troubleshooting. Compatibility with frequency converters extends the application range in modern drive systems. The devices are designed for use in industrial environments and comply with applicable standards.

The devices are designed for use in enclosures and meet the requirements of industrial electrical engineering. The certifications UL-listed C/US and UKCA confirm compliance with relevant safety and quality standards. The devices are suitable for use with frequency converters, enabling application in modern drive systems. The adjustability of voltage threshold and standstill time allows flexible adaptation to various motors and applications. The LED indicators provide visual feedback on operating status, facilitating maintenance and troubleshooting. The devices are designed for use in industrial environments and comply with applicable standards.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1153147
qrcode für Dold 0069308 UG9146.22PC/61 20-400mV 0.2-6s still-run monitor