Further information for Dold 0069089 RL5881.11/100 1K-300K insulation monitor

Technical data
Enclosure designDistribution board
IMD typeDC
Nominal voltage IT systemDC 0 - 240 V
Response value1 - 300 kΩ
Response value typeAdjustable
Width35 mm
TypeRL 5881
Earth fault indicatorYes
Variant
Alarm value1 - 300 kOhm
Auxiliary voltageWithout
Contact equipping1 changeover contact for warning
The insulation monitor RL5881.11/100 1K-300K from Dold is a device for monitoring insulation in ungrounded DC-IT systems. It belongs to the VARIMETER IMD family and is designed for continuous detection of insulation faults to ensure preventive fire and system protection. The device is designed for DC-IT networks with a nominal voltage of 0 to 240 V and is particularly suitable for applications in battery systems, UPS systems, and other ungrounded DC networks. Monitoring is also performed when the network is de-energized, enabling continuous safety monitoring.

Insulation monitoring according to IEC/EN 61557-8
The device complies with standard IEC/EN 61557-8, which applies to electrical insulation monitoring in IT systems. It detects both symmetrical and asymmetrical insulation faults, ensuring comprehensive diagnosis of insulation quality. The measurement is performed via an active measurement circuit between terminals L+ and L- and the protective earth connection PE. A measurement voltage with alternating polarity is applied to determine the insulation resistance.

Adjustable trip threshold and display
The trip threshold for insulation monitoring is adjustable in the range of 1 kΩ to 300 kΩ via a rotary switch on the device front. This allows application-specific adjustment of sensitivity. Operating states are visualized via a multicolored device status LED: green for normal operation, red for insulation fault, and orange for internal device defect. LED blink codes support fault diagnosis.

Functions and equipment in detail
The device features a changeover contact (1 changeover contact for alarm) to signal when the set trip threshold is undershot. The alarm relay operates on the rest current principle, i.e., it de-energizes on trip. The alarm message can be programmed via a control input (X2/X3) to activate either memory behavior (alarm memory) or hysteresis behavior. When memory mode is activated, the alarm message remains stored even if the insulation resistance subsequently returns to the acceptable range. Reset is performed via the Test/Reset button on the device front, which must be pressed for more than 3 seconds.

Technology explained clearly
Upon power-up, an internal self-test is performed, lasting approximately 10 seconds. This test is indicated via the status LED. Afterward, continuous measurement of insulation resistance begins. The measurement is carried out in a circuit between L+/L- and PE, with the measurement voltage being applied with alternating polarity to enable precise resistance determination.

Compatibility and accessories
The device is designed for network leakage capacitances up to 30 μF and is suitable for applications in modern DC-IT systems. It requires no additional pre-stage device. The width is 35 mm, enabling installation in standard installation distributors. The tamper-proof transparent cover protects the device against unauthorized manipulation. Control inputs for external test and reset buttons are provided to support operation in integrated systems.

Mounting and installation
Mounting is performed in an installation distributor. Terminals L+ and L- are connected directly to the DC network to be monitored, while terminal PE is connected to the protective earth network. Device power supply is via terminals L+ and L– for the RL5881/100 variant. The device front is designed for operation and adjustment, with the trip threshold rotary switch and status LED directly accessible.

Advantages in operation
The insulation monitor RL5881.11/100 1K-300K provides reliable, continuous insulation monitoring in DC-IT systems. The simple adjustment of the trip threshold and visual indication of operating states simplify maintenance and diagnosis. The integrated self-test function and the ability to store alarm messages increase safety and transparency in operation. The tamper-proof cover protects against unauthorized access, which is particularly advantageous in critical installations.