Further information for Dold 0068859 RL5889.11 DC12-24V 1K-300K insulation monitor
Technical data
Enclosure design
Distribution board
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 240 V, DC 0 - 240 V
Response value
1 - 300 kΩ
Response value type
Adjustable
Width
35 mm
Type
RL 5889
Earth fault indicator
Variant
Alarm value
1 - 300 kOhm
Auxiliary voltage
DC 12 - 24 V
Contact equipping
1 changeover contact for warning
The insulation monitor RL5889.11 from Dold is a device for monitoring insulation quality in IT systems, used in ungrounded AC, DC, and mixed AC/DC networks. The device belongs to the VARIMETER IMD family and is designed for continuous monitoring of insulation resistances in the range of 1 kΩ to 300 kΩ. It is operated via an auxiliary voltage in the range of DC 12–24 V and is suitable for installation in installation distributors with a mounting width of 35 mm. The earth fault indication is integrated, allowing the operating status to be visually monitored via a multicolored LED.
Applications
The RL5889.11 is universally applicable in various application scenarios, including ungrounded AC and DC networks, UPS systems, networks with frequency converters, battery networks, and networks with DC drives. It can also be used for insulation monitoring in hybrid and battery-powered vehicles. Monitoring is also performed when the network is de-energized, increasing reliability in critical installations. The maximum network capacitance is 30 μF, enabling use in systems with higher capacitances.
Functions and Equipment in Detail
The device is parameterized via two rotary switches on the front, allowing simple and user-friendly setting of the trip threshold and network type (AC, DC, AC/DC). The device detects both symmetrical and asymmetrical insulation faults. The operating status is indicated via a multicolored LED, which visually signals different states such as operation, alarm, or internal faults. An automatic and manual self-test ensures functional verification of the device. Storage or hysteresis behavior can be selected and programmed via a control input.
Technology Explained Simply
The insulation monitor measures the insulation resistance between terminals L(+) and L(−) and the protective earth connection PE. To do this, an active test voltage with alternating polarity is applied to determine the resistance. If the set trip threshold is undershot, the alarm relay K1, equipped as a 1 changeover contact for alarm, switches. The LED then changes to the alarm color (red). The auxiliary voltage is supplied via terminals A1(+) and A2. After switching on the auxiliary voltage, an internal self-test runs, lasting approximately 12 seconds. After that, continuous measurement begins.
Compatibility and Accessories
The device is designed for IT systems with a rated voltage of AC 0–240 V and DC 0–240 V. Insulation monitoring is performed in accordance with standard IEC/EN 61557-8. The contact configuration includes a changeover contact for alarm. A control input allows connection of an external test/reset button. The tamper-proof transparent cover protects the device against unauthorized manipulation.
Mounting and Installation
The insulation monitor is directly connected to the network to be monitored, with terminals L(+) and L(−) connected to the network voltage and PE to the protective earth network. The network type is set via the rotary switch UN. The mounting width of 35 mm allows installation in standard installation distributors. The auxiliary voltage is supplied via A1(+) and A2.
Operational Advantages
Continuous monitoring of insulation resistance achieves preventive fire and system protection. Early detection of insulation faults prevents damage and increases operational safety. Simple operation via rotary switches and visual indication via LED facilitate maintenance and diagnostics. The ability to monitor the device even when the network is de-energized increases reliability in critical installations.