Dold 0068858, EAN: 4030641688585

Dold 0068858 RL5889.11 AC/DC24-240V 1K-300K insulation monitor

Dold 0068858 RL5889.11 AC/DC24-240V 1K-300K insulation monitor

Lieske Part No. 1001668
Mfg Part No 0068858
EAN-Code 4030641688585
Manufacturer Dold
Here only 341,01 EUR
405,80 EUR incl. VAT

Further information for Dold 0068858 RL5889.11 AC/DC24-240V 1K-300K insulation monitor

Technical data
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 240 V, DC 0 - 240 V
Response value1 - 300 kΩ
Response value typeAdjustable
Width35 mm
TypeRL 5889
Earth fault indicatorYes
Variant
Alarm value1 - 300 kOhm
Auxiliary voltageAC/DC 24 - 240 V
Contact equipping1 changeover contact for warning
The isolation monitor RL5889.11 from Dold is a device for monitoring insulation quality in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks. The device belongs to the VARIMETER IMD family and is used for early detection of insulation faults to ensure preventive fire and system protection. It is designed for nominal voltages up to 240 V AC or DC and can be used in networks with frequency converters, UPS systems, battery networks, as well as in hybrid and battery-powered vehicles. Device parameterization is performed via two rotary switches on the front panel, enabling simple and user-friendly adjustment of the trip threshold and network type (AC, DC, AC/DC).

Applications

The RL5889.11 is universally applicable in various scenarios where continuous insulation monitoring is required. This includes IT systems in industrial plants, medical facilities, mobile vehicles, and systems with DC drives. Monitoring also occurs when the network is de-energized, increasing the reliability of diagnostics. The device is designed for network leakage capacitances up to 30 μF, making it suitable for systems with higher capacitances.

Functions and Equipment in Detail

The device features an adjustable trip threshold in the range of 1 kΩ to 300 kΩ, set via a rotary switch on the front panel. The trip threshold can be individually adjusted according to system requirements. The operational status is indicated by a multicolored status LED, which lights green when the device is operating normally and red in case of an insulation fault. Additionally, a ground fault is indicated by the LED. The contact configuration includes a changeover contact (11-12-14) for alarm signaling, which switches when the set trip threshold is undershot.

Technology Explained Simply

Insulation monitoring is performed in accordance with standard IEC/EN 61557-8. The device generates an active test voltage with alternating polarity between the connection terminals L(+) and L(-) and the protective earth terminal PE. This allows the insulation resistance in the network to be measured. The measurement takes place in a test circuit directly connected to the network being monitored. The network type (AC, DC, AC/DC) is selected via a rotary switch. When the trip threshold is undershot, the alarm relay K1 switches and the status LED turns red. The function of the alarm relay can be selected between operating current and rest current principle.

Compatibility and Accessories

The device is designed for auxiliary voltages in the range AC/DC 24–240 V, allowing flexible use in various supply networks. The control inputs X2/X3 enable programming of the memory behavior: when the contacts are not bridged, an insulation fault message is stored, even if the insulation resistance later returns to the acceptable range. An external test/reset button can be connected to the control input to manually reset the alarm. The tamper-proof transparent cover protects the device from unauthorized manipulation.

Mounting and Installation

The isolation monitor RL5889.11 is designed as an installation distributor with a width of 35 mm, making it suitable for standard distribution boxes. The connection terminals A1(+) and A2 are used for auxiliary voltage supply. The terminals L(+) and L(-) are connected directly to the network being monitored, while PE is connected to the protective earth network. After switching on the auxiliary voltage, an internal self-test runs for approximately 12 seconds, visualized by the status LED. Afterward, continuous insulation measurement begins.

Advantages in Operation

The RL5889.11 offers reliable and flexible insulation monitoring, detecting both symmetrical and asymmetrical faults. Simple parameterization via rotary switches and visual indication via the multicolored LED facilitate commissioning and maintenance. The ability to choose memory behavior and relay behavior (operating or rest current principle) increases adaptability to different requirements. The integrated self-test function ensures device functionality, guaranteeing operational safety. The tamper-proof cover protects against unauthorized access, which is advantageous in safety-critical applications.

fettIsolation monitor** is the central product that monitors fettIT systems. The **fettinsulation monitoring** is performed according to fettIEC/EN 61557-8. The device is designed for **fettAC/DC networks** up to 240 V and offers an fettadjustable trip threshold** from 1 kΩ to 300 kΩ.