Further information for Dold 0068685 UG9256.11/001 3AC200-480V 2A 1-10S motor starter soft start
Technical data
1- / 3-phase
3
Approvals
UL
Auxiliary voltage
DC 24 V
Load current up to
9 A
Load voltage up to
3AC 200 - 480 V
On/Off Input Control
DC
Width
22,5 mm
Type
UG 9256
Signalling output
Temperature monitoring
Variant
Contact equipping
1 changeover contact
Nominal current
2 A
Nominal voltage
3AC 200 - 480 V
Ramp time
1 - 10 s
Approvals and Markings
UL-listed C/US, UKCA
Variant
With softstart. With mains isolating relay, on when no failure. Motor protection
The intelligent motor starter UG9256 of the MINISTART series by Dold is a compact device for controlling and protecting 3-phase asynchronous motors. It enables soft start, reversing, and protection against overload and blocking. The device is designed for use in industrial applications where reliable and damage-free motor control is required. The width of 22.5 mm allows space-saving installation in standard control panels. Control is performed via digital inputs with an auxiliary voltage of DC 24 V, making integration into existing control systems simple.
Applications
The motor starter is suitable for drives in door and gate drives, bridge and lifting equipment, as well as conveyor systems, where monitoring of blocking is required. It can also be used in process control systems where safe and disturbance-free operation of drives is prioritized. The application is for motors with a power rating of 30 W to 150 W, 90 W to 750 W, or 550 W to 4 kW at an operating voltage of AC 400 V. The 3-phase design makes it suitable for standard industrial motors.
Functions and Equipment in Detail
The device features several integrated functions: soft start, soft stop, reversing in both directions, motor protection via overcurrent detection and blocking protection. Direction reversal is achieved via relays that switch without current, increasing the contact lifespan. The soft start and stop functions are implemented using thyristors, ensuring a smooth rise and fall of torque. The ramp time is adjustable between 1 and 10 seconds. Overcurrent detection is activated if the set current value is exceeded for more than 2 seconds. Settings are adjusted via potentiometers on absolute scales, enabling simple and time-saving commissioning.
Technology Explained Simply
The UG9256 combines the advantages of robust relay technology with wear-free semiconductor technology. The main functions are implemented using hybrid relays that utilize both mechanical contacts and semiconductor components. Temperature monitoring of the semiconductors ensures high device availability. The voltage rating of the semiconductors reaches up to 1500 V, ensuring high safety during voltage surges. Galvanic isolation between control and main current circuits is achieved via forced contacts with a minimum spacing of 0.5 mm, ensuring safe insulation. The load voltage can reach up to 3AC 200–480 V, and the load current up to 9 A.
Compatibility and Accessories
The device is compliant with IEC/EN 60947-4-2 and carries the certifications UL-listed C/US and UKCA. Control is performed via galvanically isolated 24 V inputs for clockwise and counterclockwise rotation. An integrated alarm output signals operational readiness. Optionally, an additional alarm output can be provided according to customer requirements. Connection options include a reset button on the device front and an external connection for a reset button.
Mounting and Installation
Mounting is done in standard control panels with a width of 22.5 mm. Device indicators consist of four LEDs that visually display the operating status. Commissioning is performed via adjustment controls on the front, with settings adjusted using potentiometers on absolute scales. Fault acknowledgment is done via the reset button or an external input.
Advantages in Operation
By combining multiple functions in one device, space requirements are reduced by up to 80%. The current-free relay switching during direction reversal extends contact lifespan. Monitoring of semiconductor temperature and high voltage rating increase operational safety. Simple operation and commissioning via potentiometers on absolute scales reduce installation time. The integrated motor protection function protects the motor against overload and blocking, minimizing downtime.