| Technical data |
| Diameter | 49 mm, 79 mm, 119 mm |
| For relay type | IL 5882, SL 5882 |
| Type | ND 5014 |
| Variant |
| Variant | 49 mm inner diameter |
The ND5014/050 hinged current transformer from Dold is a measuring current transformer for differential current measurement in electrical installations. It is used in conjunction with Dold differential current monitors IL 5882 and SL 5882 to monitor fault currents in the range of 10 mA to 30 A. The ND5014/050 size features an inner diameter of 49 mm and is therefore suitable for conductors with a maximum diameter of 49 mm. The hinged design allows for easy installation without disconnecting the current-carrying conductors, making it particularly suitable for retrofitting in existing installations.
Applications
The hinged current transformer is used for monitoring differential currents in alternating and pulsating direct current installations. It is typically used in conjunction with differential current monitors to detect fault currents that may indicate insulation faults or leakage. The application is in industrial and commercial electrical installations where continuous monitoring of electrical safety is required. Measurement is performed according to IEC/EN 62020, and the transformer is classified as type A, all-current sensitive, meaning it detects both alternating and pulsating direct currents.
Functions and Equipment in Detail
The transformer is designed for a maximum operating voltage of AC 720 V and complies with standards IEC 61869-1 and IEC 61869-8. The rated primary current is 10 A, with a nominal transformation ratio of 500:1. Accuracy is class 3, providing sufficient measurement accuracy for fault current monitoring. The nominal power is 50 mVA. The conductor connection terminals are equipped with spring clamp technology (Push-In technology), enabling quick and secure connection of conductors with a cross-section of 0.2 to 2.5 mm² (rigid or flexible). The stripping length is 6 mm.
Technology Explained Simply
The hinged current transformer operates on the principle of a current transformer, where the primary current flows through a coil and generates a magnetic field that induces a voltage in a secondary coil. This voltage is transmitted to the differential current monitor, which calculates the difference between the currents in the conductors (excluding PE). If the difference exceeds the set threshold, an alarm function is triggered. The hinged cover protects the terminal block and prevents accidental disconnection of wiring. Installation is vertical or horizontal on a DIN rail using an included plinth.
Compatibility and Accessories
The hinged current transformer ND5014/050 is specifically designed for use with Dold differential current monitors IL 5882 and SL 5882. It is not intended for use with other devices or manufacturers. Installation is via an included plinth, enabling vertical or horizontal mounting on the DIN rail. The connection terminals are marked i and k, with each appearing twice to facilitate connection to the differential current monitor.
Installation and Mounting
Installation is performed by opening the transformer, inserting the current-carrying conductors into the aperture, and closing the cover. Conductors must pass freely through the transformer to ensure accurate measurement. Mounting is done via the included plinth on the DIN rail. The maximum actuation force is 40 N. During installation, care must be taken to avoid excessive forces on the mounting feet, as these are designed to hold the transformer itself and cannot absorb forces from the conductors passing through.
Operational Advantages
The hinged current transformer offers simple and quick installation, especially for retrofits in existing installations, as no conductors need to be cut. The Push-In technology of the terminals ensures a secure and reliable connection. The hinged cover protects the connection terminals and prevents accidental disconnection of wiring. The construction is designed for an ambient temperature range of -40 °C to +80 °C, enabling broad application in various industrial environments. Insulation coordination complies with IEC 61869-1, with a rated impulse withstand voltage of 8 kV and a pollution degree of 3. The flammability class is V0 according to UL94, ensuring high safety in fire hazard situations.