Further information for Dold 0068304 RR5887.12/001 AC/DC24-80V insulation fault detector
Technical data
Bus interface
Modbus RTU, RS-485
Nominal voltage IT system
DC, AC, 3AC 24 - 455 V
Operating mode
Slave
Width
105 mm
Type
RR 5887
Failure storage
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
2 changeover contacts
Variant
For industrial plants. 8 measuring channels
The insulation fault detection device RR5887.12/001 AC/DC24-80V from Dold is a specialized device for monitoring and locating insulation faults in complex, isolated AC/DC networks (IT systems). It is used in conjunction with the test current generator RR 5886 to monitor electrical insulation in industrial plants, shipbuilding, plant engineering, and photovoltaic installations. The device is designed for use in IT systems with nominal voltages of DC, AC, and 3AC in the range of 24 to 455 V. Operation is performed as a slave, enabling it to work synchronously in a network of multiple devices via an RS-485 bus connection to increase the number of measurement channels. The RR5887.12/001 variant features 8 measurement channels, each of which can be equipped with external current transformers. These current transformers operate independently and are calibrated by the device, enabling precise fault localization.
Applications
This device is specifically designed for use in industrial plants, where the availability and operational safety of electrical systems are critical. It is particularly suitable for applications in process industry, shipbuilding, plant engineering, and photovoltaic installations, where IT systems are used to ensure power supply reliability. The ability to detect and locate insulation faults early contributes to rapid fault resolution and minimizes downtime.
Functions and Equipment in Detail
The insulation fault detection device offers two different alarm levels, indicated by LED displays (yellow for pre-alarm, red for alarm). A pre-alarm condition is triggered at an insulation fault current exceeding 1 mA, and an alarm at over 5 mA. The status output is provided via an external switching output connected to terminals G and H. Additionally, the device includes a summation alarm relay with two changeover contacts, used for outputting pre-alarm and alarm conditions. A push-button allows manual reset of alarm conditions and testing of the current transformers and their calibration. Fault memory can be activated and configured via bridge X1-X2, ensuring the alarm state is retained even after switching off the auxiliary voltage.
Technology Explained Simply
The operation is based on measuring insulation faults via external current transformers connected to the measurement channels. The test current generator RR 5886 generates a test current that is fed through the network. The RR 5887 detects the effect of this current at individual measurement channels and evaluates whether an insulation fault exists. Communication is via an RS-485 bus connection, enabling both synchronization of test current evaluation and connection to a Modbus RTU fieldbus system. The auxiliary voltage can range from AC/DC 24 to 80 V, allowing universal adaptation to various supply networks. The width is 105 mm, enabling installation in standard control panels.
Compatibility and Accessories
The device is specifically designed for use with the test current generator RR 5886, which provides the necessary test current supply. Communication is via RS-485, allowing multiple RR 5887 devices to be networked to increase the number of measurement channels. The terminal blocks are designed for connection to external current transformers, the RS-485 bus, and switching outputs. Terminal designations include A1/A2 for auxiliary voltage, K1 to K4/I1 to I4 for current transformers, SH, GND, Rb, B, A, Ra for the RS-485 bus, X1/X2 for the switching input, and G/H for the status output and alarm relay contacts 11/12/14 and 21/22/24 for pre-alarm and alarm.
Mounting and Installation
Mounting is in standard control panels with a width of 105 mm. The terminal blocks are clearly labeled, enabling simple and secure wiring. The current transformers are connected to the measurement channels, with calibration performed by the device. The RS-485 bus connection is established via terminals SH, GND, Rb, B, A, Ra, ensuring galvanic isolation. Functions such as alarm memory and manual reset can be configured via terminals X1/X2 and the push-button.
Advantages in Operation
Early detection of insulation faults enables targeted and rapid repair, increasing operational safety and minimizing downtime. Simple operation via clear adjustment elements and automatic calibration reduces maintenance effort. The ability to connect multiple devices via RS-485 expands application possibilities in large, distributed networks. The universal auxiliary voltage range of AC/DC 24–80 V increases installation flexibility. Fault memory ensures the state is documented even after a power failure, which is helpful for fault analysis.