Dold 0068302, EAN: 4030641683023

Dold 0068302 RR5886 AC/DC24-80V test current generator

Dold 0068302 RR5886 AC/DC24-80V test current generator

Lieske Part No. 1002093
Mfg Part No 0068302
EAN-Code 4030641683023
Manufacturer Dold
Here only 1.108,54 EUR
1.319,16 EUR incl. VAT

Further information for Dold 0068302 RR5886 AC/DC24-80V test current generator

Technical data
Bus interfaceModbus RTU, RS-485
Nominal voltage IT systemDC, AC, 3AC 24 - 455 V
Operating modeMaster / Slave
Width105 mm
TypeRR 5886
Variant
Auxiliary voltageAC/DC 24 - 80 V
VariantFor industrial plants
The RR5886 test current generator from Dold is a device for insulation fault detection in complex, isolated AC/DC networks (IT systems). It is used in conjunction with the insulation fault detection device RR5887 to monitor and locate insulation faults. The device is designed for use in industrial plants and supports an auxiliary voltage in the range of AC/DC 24 to 80 V. The width is 105 mm, enabling installation in standard control panels. Operation is in master/slave mode, where multiple devices can be connected via an RS-485 bus connection to increase the number of measurement channels. This enables more precise fault localization in extensive networks.

Applications

The RR5886 is designed for monitoring IT systems with nominal voltages of DC, AC, and 3AC in the range of 24 to 455 V. It is used in industry, shipbuilding, plant engineering, and photovoltaic installations. The combination with the RR5887 enables compliance with standards DIN EN 61557-9 (VDE 0413-9):2009 and DIN EN 61557-1 (VDE 0413-1), which apply to insulation fault detection in electrical installations. Insulation coordination is carried out according to IEC 60664-1, ensuring the safety and reliability of the system.

Functions and Equipment in Detail

The device generates positive and negative test currents to monitor DC networks as well as networks with simultaneous AC and DC components. The test current output can be manually initiated via a button or externally controlled via terminal connections (Y1, Y2). Shorting terminals Y1-Y2 disables the button. The test current output depends on the bus mode, with exact timing controlled via the RS-485 connection. The status output of the insulation fault detection is provided via an external switching output (G, H).

Technology Explained Simply

The test current generator operates with external current transformers, which function independently and are connected to the measurement channels of the RR5887. These are calibrated by the RR5887, enabling accurate evaluation of fault currents. The RS-485 bus connection is used for synchronizing test current evaluation and can optionally be used for Modbus RTU fieldbus connection. The Modbus RTU interface allows control of insulation fault detection and reading of fault currents. Indication is provided via LEDs: a green LED ON" indicates that the operating voltage is present. A yellow LED "BUS indicates bus activity, while additional yellow LEDs indicate the output of positive and negative test current pulses.

Compatibility and Accessories

The RR5886 is specifically designed for use with the insulation fault detection device RR5887. The combination enables localization of insulation faults in complex networks. External control via an insulation monitor is possible, facilitating integration into existing monitoring systems. The RS-485 bus connection allows chaining multiple devices, increasing the number of measurement channels and refining fault localization.

Mounting and Installation

The device is mounted in standard control panels, with a width of 105 mm representing a common installation width for industrial devices. Connections are made via terminals: A1(+), A2 for auxiliary voltage, L1(+), L2(-), L3, PE for IT network voltage connections. The RS-485 bus connection is made via terminals SH, GND, Rb, B, A, Ra, which are galvanically isolated. Control of the test current output is via Y1, Y2, and status output via G, H.

Operational Advantages

Early detection and localization of insulation faults enable quick and targeted remediation. Automatic adjustments and clear design of the control elements allow for simple and intuitive operation. Two alarm levels support timely detection of dangerous insulation conditions. This increases the operational safety and high availability of the network. The universal auxiliary voltage of AC/DC 24 to 80 V increases flexibility during installation in various plants.
This is an offer of: