Further information for Dold 0068221 RR5887.12 AC/DC85-230V insulation fault detector
Technical data
Bus interface
Modbus RTU, RS-485
Nominal voltage IT system
DC, AC, 3AC 24 - 455 V
Operating mode
Slave
Width
105 mm
Type
RR 5887
Failure storage
Variant
Auxiliary voltage
AC/DC 85 - 230 V
Contact equipping
2 changeover contacts
Variant
For industrial plants. 4 measuring channels
The insulation fault locator RR5887.12 AC/DC85-230V from Dold is a specialized device for monitoring and locating insulation faults in complex, isolated AC/DC networks, i.e. IT systems. It is used in conjunction with the test current generator RR 5886 and serves for continuous monitoring of insulation quality in industrial plants, shipbuilding, plant engineering, and photovoltaic installations. The device enables fast and targeted correction of insulation faults, thereby increasing the operational safety and availability of the power network.
Applications
The device is designed for use in industrial environments, particularly in plants with isolated networks, where interruption of power supply is not acceptable. It is used in process industry, power generation, especially in PV installations, and in ship technology. The ability to detect insulation faults in AC, DC, and combined AC/DC networks makes it universally applicable. Localization is achieved via connection to external current transformers, which operate independently and are connected to the device's measurement channels.
Functions and Equipment in Detail
The insulation fault locator features 4 measurement channels, to which an external current transformer can be connected individually. The current transformers are calibrated by the device, ensuring high measurement accuracy. Indication is provided via LED indicators: yellow LEDs signal a warning when insulation fault current exceeds 1 mA, red LEDs indicate an alarm when fault current exceeds 5 mA. Status indication is also provided via an external switching output. Two different alarm levels allow for differentiated response to the insulation condition. A push-button is used for manual reset of alarm states and for testing the current transformers and their calibration.
Technology Explained Simply
The device operates as a slave in a system consisting of the test current generator RR 5886 and multiple insulation fault locators. Communication takes place via an RS-485 bus connection, enabling synchronization of test current evaluation. Optionally, the bus connection can also be used for Modbus RTU fieldbus connection, facilitating integration into higher-level control systems. The auxiliary voltage is AC/DC 85–230 V, allowing universal adaptation to various power supplies. Insulation coordination is according to IEC 60664-1, ensuring safety and reliability of the device in electrical installations. The slave operation means the device performs its functions under the control of a central device (e.g. the test current generator).
Compatibility and Accessories
The device is specifically designed for use with the test current generator RR 5886, which generates the necessary test currents. Communication occurs via RS-485, allowing multiple insulation fault locators to be connected, thereby increasing the number of measurement channels. This enables detailed fault localization in extensive networks. The terminal blocks are designed for connecting current transformers, the RS-485 bus connection, and switching outputs. The width is 105 mm, enabling installation in standard control panels.
Mounting and Installation
Mounting is in standard control panels with a width of 105 mm. The terminal blocks are clearly labeled, enabling easy wiring. The current transformers are connected to measurement channels K1 to K4. The RS-485 bus connection is made via terminals SH, GND, Rb, B, A, Ra. The switching input (X1, X2) can be activated either via a wire bridge or via an external device with max. 24 V DC to control the alarm memory function. The function is active-low, meaning the memory function is activated when a low level is applied.
Operational Advantages
Early detection of insulation faults enables targeted and rapid correction, minimizing downtime. Simple operation through automatic calibration and clear adjustment elements reduces error susceptibility during commissioning. Fault memory via bridge X1-X2 enables documentation of alarm states, which is helpful for maintenance and failure analysis. Integration into Modbus RTU systems enables centralized monitoring and control, increasing the efficiency of operational monitoring. The universal auxiliary voltage of AC/DC 85–230 V makes the device flexible for use in various plant configurations.
Summation Alarm Relays
The device features two summation alarm relays: one for warning (contacts 11, 12, 14) and one for alarm (contacts 21, 22, 24). Both are changeover contacts, enabling flexible use in various circuits. Output of status information via external switching outputs enables integration into alarm and control systems.
Compliance with Standards
Insulation fault detection is carried out according to DIN EN 61557-9 (VDE 0413-9):2009 and DIN EN 61557-1 (VDE 0413-1), ensuring compliance with applicable standards for electrical monitoring technology. Insulation coordination according to IEC 60664-1 ensures electrical safety of the device in industrial applications.
Operating Mode and Communication
As a slave device, the RR5887.12 operates under the control of the test current generator RR 5886. Communication takes place via RS-485, allowing multiple devices to be connected. The Modbus RTU fieldbus connection enables integration into higher-level control systems. Bus activity is indicated by a yellow LED (BUS), facilitating diagnosis of communication issues.
Fault Memory
Fault memory can be activated via the switching input X1-X2. When activated, alarm states are stored even if the fault is no longer present at the moment. This enables retrospective analysis and documentation of disturbances.
Terminal Blocks
The terminals are clearly labeled: A1(+), A2 for auxiliary voltage, K1 to K4/I1 to I4 for current transformers, SH, GND, Rb, B, A, Ra for RS-485 bus connection, X1, X2 for switching input, G, H for switching output, and 11, 12, 14 as well as 21, 22, 24 for alarm relays. The terminals enable secure and reliable connection of external components.
LED Indicators
The green LED ON" indicates that the operating voltage is present. The yellow LEDs for channels 1 to 4 signal a warning when insulation fault current exceeds 1 mA. The red LEDs for channels 1 to 4 indicate an alarm when fault current exceeds 5 mA. The yellow LED "BUS indicates activity of the RS-485 bus connection.
Insulation Fault Detection IT Systems Modbus RTU RS-485 Test Current Generator Summation Alarm Relays