Further information for Dold 0068125 semiconductor relay PH9270.91/002 AC200-480V AC3A
Technical data
Load current up to
40 A
Load voltage up to
AC 480 V
Number of poles
1-pole
On/Off Input Control
DC
Width
45 mm
Type
PH 9270
Signalling output
Variant
Auxiliary voltage
DC 24 V
Load current
AC 3 A
Load voltage
AC 200 - 480 V
Semiconductor output
1-pole
Variant
Switching at zero crossing. With over current monitoring and PNP transistor output with de-energized on trip. Without heat sink
The Dold semiconductor relay PH9270.91/002 AC200-480V AC3A is a 1-pole AC semiconductor relay/contact, designed for wear-free and noiseless switching as well as continuous monitoring of load circuits in industrial applications. It is particularly suitable for use in systems with heaters, motors, valves, and lighting systems, where high switching frequency and reliability are required. The device operates on the zero-voltage switching principle, meaning switching occurs at the zero crossing of the sinusoidal mains voltage, minimizing voltage spikes and electromagnetic interference. Control is digital via a DC interface with an auxiliary voltage of 24 V DC.
Applications
This semiconductor relay is used in various industrial machines and systems, including injection moulding machines in the plastics and rubber industry, extruders, thermoforming and blow-moulding machines, packaging machines, soldering systems, and food industry machinery. The integrated load circuit monitoring enables early detection of faults such as load circuit interruption, over- or under-current, missing load voltage, fuse failure, or thyristor defects. In case of over-current monitoring, the control system must include a start-up bypass time to account for the inrush current of motors or other inductive loads.
Functions and Equipment in Detail
The device features integrated load circuit monitoring, which continuously monitors load voltage and load current when auxiliary voltage (A3+/A2) is applied. If deviations from the set load current limit, interruption of the load circuit, or failure of a power semiconductor occur, an alarm output is activated. The alarm output is implemented as a PNP semiconductor signal output and operates on the rest current principle, meaning it activates in the event of a fault. Status indication is provided by a dual-color LED: the LED A1/A5,1 cm ( 2 inch ) indicates the status of the control input (yellow = activated, off = not activated), while the LED "Alarm signals the device status (green = no fault, red = fault, off = no auxiliary voltage). The load voltage is AC 200 to 480 V, the load current is AC 3 A, with the device designed for a maximum load current of 40 A (AC 51).
Technology Explained Simply
The PH9270.91/002 is based on DCB technology (Direct-Copper-Bonding process), ensuring optimal heat dissipation and thus increasing the device's lifespan. It consists of two antiparallel-connected thyristors, enabling bidirectional current flow. The zero-voltage switching ensures that the relay turns on at the next zero crossing of the mains voltage and turns off at the next zero crossing of the load current. This reduces thermal stress and prevents unwanted electrical interference. The device is delivered without a heatsink, although an optional heatsink for mounting on DIN rail is available.
Compatibility and Accessories
The semiconductor relay is compliant with IEC/EN 60947-4-3 and designed for use in industrial control systems. It is PLC-compatible and can be integrated into existing automation systems. Control is via a digital DC input, with an auxiliary voltage of 24 V DC. The width is 45 mm, enabling compact mounting in standard control panels. An optional over-temperature protection device is available, where a temperature limit switch (normally open) can be inserted into a designated pocket at the bottom of the device. If the heatsink temperature exceeds 100 °C, the switch opens and protects the device from thermal overload. An example of a suitable temperature limit switch is the UCHIYA type UP62–100.
Mounting and Installation
Mounting is done in standard control panels or on DIN rail. Installation must only be carried out by a qualified electrician. The connection terminals are clearly labeled: A1+/A2 for the control input, A3+/A2 for the operating voltage and load circuit monitoring, Alarm for the semiconductor signal output, L1 for the mains connection, and T1 for the load output. The width of 45 mm allows for compact placement in enclosures. The touch protection class is IP 20, suitable for use in enclosed control systems.
Advantages in Operation
The device offers wear-free and noiseless switching, increasing lifespan and extending maintenance intervals. The integrated load circuit monitoring enables rapid fault detection and localization, enhancing operational safety. The dual-color LED display provides visual feedback on the operating status, simplifying fault diagnosis. The DCB technology ensures efficient heat dissipation, reducing thermal stress and increasing reliability in continuous operation. The device is designed for industrial environments where high switching frequencies and continuous monitoring are required.