Further information for Dold 0067800 HS PH9270.91/003 AC48-480V AC45A
Technical data
Load current up to
45 A
Load voltage up to
AC 480 V
Number of poles
1-pole
On/Off Input Control
DC
Width
45 mm
Type
PH 9270/003
Signalling output
Variant
Analogue output
DC 0 - 10 V
Auxiliary voltage
DC 24 V
Load current
AC 45 A
Load voltage
AC 48 - 480 V
Semiconductor output
1-pole
Variant
Switching at zero crossing. With analogue output. Without heat sink
The semiconductor relay PH9270.91/003 from Dold is an AC semiconductor relay with integrated load current measurement, designed for use in industrial applications with alternating voltage up to AC 480 V and load currents up to 45 A. It features an analogue output in the range DC 0 – 10 V, which continuously monitors the load current and provides a proportional signal. Control is achieved via DC actuation with auxiliary voltage DC 24 V. The device is designed as a zero-voltage switch, meaning it activates at the next zero crossing of the sinusoidal supply voltage and deactivates at the next zero crossing of the load current. This switching method ensures excellent EMC properties and minimizes disturbances in the network. The width is 45 mm, enabling compact mounting on the DIN rail.
Applications
This semiconductor relay is particularly suitable for applications involving heating processes, where early fault detection is required. It is commonly used in plastic and rubber injection moulding machines, thermoforming and packaging machines, as well as in the food industry. Continuous monitoring of the load current enables precise control and diagnosis of processes, thereby increasing productivity.
Functions and equipment in detail
The device continuously measures the load current and converts it into an analogue output signal, which can be directly evaluated by a PLC or an analogue input display module. The measurement is performed as true RMS, ensuring an accurate representation of actual current consumption. The LED indicator on the device shows the status of the control input: yellow indicates that the relay is activated, while off indicates it is not activated. The DCB technology (Direct-Copper-Bonding process) ensures optimal heat dissipation and contributes to thermal stability.
Technology explained simply
The semiconductor relay operates using two antiparallel-connected thyristors that control the current flow. The zero-voltage switching minimizes electrical interference, as switching always occurs at a voltage zero point. This is particularly important in sensitive industrial environments to maintain power quality. The analogue output enables easy integration into existing control and monitoring systems, as the signal can be processed directly. The load voltage can range from AC 48 to 480 V, with a frequency between 47 and 63 Hz.
Compatibility and accessories
The device is compliant with IEC/EN 60947-4-3 and designed for use in industrial control systems. Optionally, it is available with a heatsink, which clips onto the DIN rail and improves heat dissipation. For thermal protection, a temperature limit switch (normally open) can be inserted into a designated pocket on the device. As an example, the type UP62 – 100 from UCHIYA is mentioned, which opens the contact at a temperature of 100 °C.
Mounting and installation
Mounting is done on the DIN rail, with the width of 45 mm allowing for compact placement. Terminal markings are clearly defined: A1+/A2 for the control input, A3+/A2 for the operating voltage and load current measurement, Out for the analogue output, L1 for the mains connection, and T1 for the load output.
Advantages in operation
The relay is wear-free, noiseless, and economical in operation. The integrated load current measurement enables precise control and early fault detection. The excellent EMC properties and zero-voltage switching ensure stable and interference-free operation. The simple integration into PLC systems via the analogue output reduces control complexity and increases system reliability.