| Technical data |
| Approvals | UL, UL-Recognized |
| Load current up to | 88 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC, AC/DC, DC |
| Width | 22,5 mm |
| Type | PK 9260 |
| Variant |
| Control voltage | AC 100 - 230 V |
| Load current | AC 20 A |
| Load voltage | AC 48 - 480 V |
| Semiconductor output | 1-pole |
| Approvals and Markings | UL-listed C/US |
| Variant | Switching at zero crossing. M4 flat terminal. With heat sink |
The Dold semiconductor relay PK9260.91/000/04 AC48-480V AC20A is an
AC semiconductor relay designed for industrial applications, particularly for wear-free and noiseless control of resistive loads such as heaters, cooling systems, or lighting installations. The device operates on a
zero-voltage switching technique, where the output is activated at the next zero crossing of the sinusoidal mains voltage as soon as the control voltage is applied. After removal of the control voltage, the relay switches off at the next zero crossing of the load current. This switching method minimizes electrical interference and extends the device’s service life. The integrated
LED indicator visually signals the status of the control input.
Applications
This semiconductor relay is designed for use in machine building and automation technology, for example in injection molding machines, packaging machines, soldering systems, or food industry equipment. It is suitable for applications requiring high switching frequency and long service life without mechanical contacts wearing out. The
noiseless operation makes it particularly suitable for environments where noise reduction is important.
Functions and Features in Detail
The device features a
single-pole semiconductor output and is rated for a load voltage of AC 48 to 480 V and a load current of AC 20 A. The control voltage range is AC 100 to 230 V. Control is digital via AC, AC/DC, or DC. The
M4 flat terminal enables a secure and quick connection. The
DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, reducing thermal stress and increasing reliability. The
peak blocking voltage is up to 1600 V, and the
insulation voltage is 4000 V, ensuring high electrical safety.
Technology Explained Simply
The relay operates with two antiparallel-connected thyristors, enabling current flow in both directions. The zero-voltage switching ensures that switching always occurs at a current zero crossing, preventing spark generation and electrical interference. The
on-delay is up to 10 ms plus half a mains cycle, and the
off-delay is up to 35 ms plus half a cycle, with the exact delay depending on the control voltage. The width of
22.5 mm makes the device space-saving for enclosures.
Compatibility and Accessories
The semiconductor relay is specified according to
IEC/EN 62314 as well as
IEC/EN 60947-4-2 and -4-3 and carries the approval
UL-listed C/US. It is designed for use in AC-51 operating modes, with a maximum load current of up to 88 A. The variant is equipped with a
heat sink, which can be snap-mounted onto a DIN rail. Alternatively, the device can be mounted onto existing cooling surfaces using two screws. The heat sink option facilitates heat dissipation under higher loads and supports selection of the appropriate variant depending on environmental conditions.
Mounting and Installation
Mounting is either directly onto a cooling surface using two screws or via the integrated heat sink onto a DIN rail. When mounting multiple relays side by side, sufficient cooling and ventilation must be ensured to avoid overheating. The connection terminals are designed for secure connections, with the M4 flat terminal being the specified variant. Control is via terminals A1(+) and A2, where L1 is the mains connection and T1 is the load output.
Operational Advantages
The device offers high switching frequency and long service life due to its wear-free semiconductor control. The
noiseless operation and
vibration and shock resistance make it suitable for demanding industrial environments. The
space-saving design with a width of 22.5 mm enables efficient use of enclosure space. The integrated LED indicator simplifies diagnosis and maintenance, as the status of the control input is directly visible. The
UL approval ensures suitability for use in the USA and Canada.
Approvals and Standards
The device complies with standards
IEC/EN 62314 and
IEC/EN 60947-4-2 and -4-3. The
UL-listed C/US approval confirms compliance with safety requirements in North America. The insulation voltage of 4000 V and peak blocking voltage of 1600 V guarantee high electrical safety.
Functional Safety
The device does not feature an integrated over-temperature alarm function. For variants with fans, the user is required to implement measures to detect fan failure, as this could lead to fire hazard. Safety instructions are detailed in the datasheet.